The power factor does not match the i...
Please check the register addresses. The register address for the present value of the power factor of each phase is “0789”. There are the register... More Details >>
Active energy (lower digit indication...
Regardless of setting, the value of the default digit length is replied. When the register address “1304” for 6-digit display is set, the value varies w... More Details >>
Replied value on the communication op...
(A) Measurement values As for the measurement elements on the test mode screen, the set values are displayed. As for the other measurement elements, 0 is ... More Details >>
Accuracy class index of active energy
Accuracy class index of active energy is a number which gives the limits of the permissible percentage error as defined in the IEC62053-22. More Details >>
Availability for battery exchange for...
The battery of the Logging unit (ME-0000BU-SS96) is NOT exchangeable. Please order a new unit. More Details >>
Wire length for analog output and con...
It depends on the service conditions. Refer to the following guidelines. ① Contact output Contact output for ME96 series is no-voltage "a" contact. The... More Details >>
Branch connection for MODBUS RTU comm...
No, it is impossible. But Multi-drop connection is possible. For details, refer to connection examples as below. More Details >>
51-57 of Total 57