  • Torque limit value change

    The torque limit value can be changed regardless of JOG operation status.Set the new torque limit value with "[Cd.22] New torque value/forward new torque val... More Details >>

    • No:23609
    • Release Date:2018/09/14 15:09
  • BUSY signal

    The BUSY signal turns ON even when position control of movement amount "0" is executed.However, since the ON time is short, the ON status may not be detected... More Details >>

    • No:23612
    • Release Date:2018/09/14 15:09
  • Motor rotation direction

    Change the direction with "[PA14] Rotation direction selection/travel direction selection". More Details >>

    • No:23587
    • Release Date:2018/09/14 15:09
  • Electronic gear

    Set "[Pr.3] Movement amount per rotation" to "36000000(360.00000degree)", and "[Pr.4] Unit magnification" to "1".The same result is obtained by setting "3600... More Details >>

    • No:23586
    • Release Date:2018/09/14 15:09
  • Current value change

    The following shows the procedure for changing the current value to a new value.(1) Write the new current value to "[Cd. 9] New current value".(2) Write "900... More Details >>

    • No:23585
    • Release Date:2018/09/14 15:09
  • BUSY signal

    No. The motors' operation is not completely linked to ON/OFF timing of the BUSY signals.BUSY signal is turned ON when the controller starts sending commands ... More Details >>

    • No:23611
    • Release Date:2018/09/14 15:09
  • Speed change during JOG operation

    Yes. The speed can be changed during JOG operation.Set the new speed with "[Cd.14] New speed value", and then set "[Cd.15] Speed change request" to "1". More Details >>

    • No:23606
    • Release Date:2018/09/14 15:09
  • Torque limit

    Set the torque limit value in "[Cd.101] Torque output setting value" before the positioning start.The values of "[Pr.17] Torque limit setting value" and "[Cd... More Details >>

    • No:23583
    • Release Date:2018/09/14 15:09
  • Warning

    No, execute "[Cd.5] Axis error reset" to cancel the error after eliminating the error cause. More Details >>

    • No:23580
    • Release Date:2018/09/14 15:09
  • Torque limit

    Torque is limited by the lower set value of "[Pr.17] Torque limit setting value" and "[Cd.22] New torque value/forward new torque value".When the current tor... More Details >>