FAQ


FAQAbout Products
FAQ
Keyword Search
Controllers
FAQ within [ Controllers ]
-
Necessity of terminating resistors in CC-Link communication
No, it is unnecessary. Terminating resistors are only required at both ends of the network. More Details >>
- No:22966
- Release Date:2018/09/03 17:31
- Category: Network related products
-
"[ ]" in the CC-Link remote I/O modules' model name "AJ65[ ]BT" represents as follows: - None: Standard type - S: Compact type - F: Low profile waterpro... More Details >>
- No:22974
- Release Date:2018/09/03 17:31
- Update:2018/09/25 17:12
- Category: Network related products
-
Settings required for transient transmission
The routing parameter settings are required for transient transmission to the CPU module with another network No. The request source station, relay station,... More Details >>
- No:22995
- Release Date:2018/09/03 17:31
- Update:2018/09/25 17:40
- Category: Network related products
-
Using a FROM/TO instruction after AJ71UC24 is replaced with QJ71C24N
I/O signals and buffer memory addresses need to be changed but data communications can be conducted using a FROM/TO instruction and X/Y signals. More Details >>
- No:23017
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Effect on sequence scans in MELSECNET/H networks
It is necessary to reduce the link refresh time of the MELSECNET/H network in order to reduce the scan time. The link refresh time can be reduced by reducin... More Details >>
- No:23018
- Release Date:2018/09/03 17:31
- Update:2018/09/26 09:27
- Category: Network related products
-
Use CC-Link dedicated cables. General-purpose cables cannot be used. More Details >>
- No:23027
- Release Date:2018/09/03 17:31
- Category: Network related products
-
RS-485 connection between LJ71C24 and an external device
Short between SDA and RDA and between SDB and RDB, and then connect them to + (Data-A) and - (Data-B) on the external device. More Details >>
- No:23048
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Unit of receive data used by the QJ71C24N series pre-defined protocol support function
The fixed data is used for specific codes and character strings such as a command. Setting a device is not required. More Details >>
- No:23049
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Link data from communication error stations in a CC-Link network
The remote input RX of the master station and the remote input RX and remote output RY of local stations clear/hold the data from an error station according ... More Details >>
- No:23057
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Refresh timing of bit data and word data in the same CC-Link station
Cyclic data is sometimes separated into new and old data by two words (32 bits) with auto refresh timing. Checking "Block data assurance per station" of the ... More Details >>
- No:23058
- Release Date:2018/09/03 17:31
- Category: Network related products
141-150 of Total 1123