How to make the expanded cyclic setting for CC-Link local stations
Make the expanded cyclic setting for a CC-Link local station using the programming tool, GX Developer or GX Works2. Follow the procedure below. (1) Set th... More Details >>
- No:23030
- Release Date:2018/09/03 17:31
- Update:2018/09/26 10:17
- Category: Network related products
-
Links with a CC-Link local station cannot be made
Check the following points. (1) CC-Link cables have been properly connected. (2) Station numbers and the transmission speed have been correctly set. (3)... More Details >>
- No:23033
- Release Date:2018/09/03 17:31
- Update:2018/09/26 10:22
- Category: Network related products
-
Unit of the receive data length used by the QJ71C24N series pre-defined protocol support function
The receive data length of the variable is specified in bytes. More Details >>
- No:23037
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Limitation on the number of levels of cascade connections when QJ71E71-100 is used
If a repeater hub is used, 10BASE-T allows a maximum of four levels of cascade connections and 100BASE-TX allows a maximum of two levels of cascade connectio... More Details >>
- No:23040
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Connecting terminating resistors for CC-Link communication
Connect terminating resistors to both ends of physical cables.A master station is not necessarily required to be connected to either end of its network. More Details >>
- No:23046
- Release Date:2018/09/03 17:31
- Category: Network related products
-
RS-485 connection between LJ71C24 and an external device
Short between SDA and RDA and between SDB and RDB, and then connect them to + (Data-A) and - (Data-B) on the external device. More Details >>
- No:23048
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Identifying disconnected CC-Link stations
Identify disconnected stations using either of the following methods. (1) Select [Diagnostics] -> [CC-Link Diagnostics].from the menu in GX Works2 or G... More Details >>
- No:23053
- Release Date:2018/09/03 17:31
- Update:2018/09/26 10:59
- Category: Network related products
-
Using Ethernet UTP cables for the CC-Link IE Controller
Ethernet UTP cables cannot be used. More Details >>
- No:23062
- Release Date:2018/09/03 17:31
- Category: Network related products
-
CD terminal setting of the QJ71C24N
"The CD terminal is not checked" has been set by default. More Details >>
- No:23065
- Release Date:2018/09/03 17:31
- Category: Network related products
-
The FX3U-ENET-L does not support the DHCP function. Set the fixed IP address using FX Configurator-EN-L. (FX Configurator-EN-L can be downloaded from Mitsubi... More Details >>