FAQ


FAQAbout Products
FAQ
Keyword Search
Controllers
FAQ within [ Controllers ]
-
Regarding the differences between CC-Link IE TSN and CC-Link IE Field Networks
(1)Whether or not networks can be mixed on the same trunk line is different. CC-Link IE TSN allows network mixing on the same trunk line. When using a CC-Li... More Details >>
- No:39359
- Release Date:2023/01/12 17:10
- Category: MELSEC iQ-F Series , Network/Communication
-
Regarding performing Data Logging with Special Relays
It's possible. Using special relays, it is possible to perform data logging from a program. For details, see the manual below. MELSEC iQ-F FX5 User's Manu... More Details >>
- No:39327
- Release Date:2023/02/14 09:05
- Category: MELSEC iQ-F Series , CPU Module
-
Storage media of a project file
The project file written in the write-inhibited media, such as FD, CD-R, or CD-RW, cannot be read. (Condition: The standard Windows status without CD-R/RW w... More Details >>
- No:25007
- Release Date:2019/04/23 11:11
- Category: MELSEC-F Series , Engineering Software
-
Remote maintenance can be performed by writing a program to a memory cassette and sending the program or by using a personal computer (GX Developer). With a ... More Details >>
- No:24998
- Release Date:2019/04/23 10:38
- Category: MELSEC-F Series , Main Unit
-
Yes, it is possible. To set the programmable controller to RUN again, while the programmable controller is stopped, set the built-in RUN/STOP switch as follo... More Details >>
- No:24965
- Release Date:2019/04/23 07:18
- Category: MELSEC-F Series , Main Unit
-
Connecting the FX3U-ENET-L whose parameters have not been set
When writing parameters first time, write the parameters for Ethernet (data of FX Configurator-RN-L) from a personal computer to a programmable controller ma... More Details >>
- No:24790
- Release Date:2019/02/28 09:08
- Category: MELSEC-F Series , Network/Communication
-
Warning 093CH (Home position return data incorrect) occurs when the backup data for absolute position restoration is lost.Execute the machine home position r... More Details >>
-
Set "[Pr.45] Home position address" of the basic parameters for home position return • Axis 1 to 16: 72+150n, 73+150n • Axis 17 to 32: 1000072+150n, 1000073+... More Details >>
-
Causes to why SD1286 does not turn on during socket communication of LCPU
Check the following. - Whether the external device specifies the port number of the corresponding connection to the L series CPU. - In the TCP fixed-length... More Details >>
- No:22787
- Release Date:2018/09/03 17:30
- Update:2018/09/22 11:51
- Category: MELSEC-L Series
-
Method to prevent the BAT.LED from turning on
To prevent an LED from turning on when an error occurs, set 0 to the relevant factor number setting area (4 bits for each) in SD207 to SD209. To disable the ... More Details >>
- No:22754
- Release Date:2018/09/03 17:29
- Category: MELSEC-L Series
451-460 of Total 1123