FAQ


FAQAbout Products

FAQ
Keyword Search
Controllers
FAQ within [ Controllers ]
-
Regarding input of Differential Driver Output Type
It does not. The built-in high-speed counter function of the FX5U/FX5UC CPU module does not support DC5V input. DC5V input can be achieved by adding BUS con... More Details >>
- No:39350
- Release Date:2023/01/12 17:09
- Update:2025/03/07 13:25
- Category: MELSEC iQ-F Series , CPU Module , High-Speed Counter
-
Regarding the number of FX5-4A-ADP connections
Up to 4 FX5-4A-ADPs can be connected to an FX5U/FX5UC/FX5S CPU module. To connect 3 or more FX5-4A-ADPs, the FX5-4A-ADP must have a serial number S/N: 224... More Details >>
- No:39348
- Release Date:2023/02/15 10:16
- Category: MELSEC iQ-F Series , CPU Module , Analog
-
Regarding the procedure for functions set in GX Works3
This is possible with the Guidance flow function. On GX Works3, you can view the setting procedure for the function you want to use. *It is supported by GX ... More Details >>
- No:39341
- Release Date:2023/02/14 17:29
- Category: MELSEC iQ-F Series , CPU Module , Engineering Software
-
Regarding the FX5S CPU Module Line-up
The line-up of input and output points of the FX5S CPU module is as follows. ・30 points (Input: 16 points, Output: 14 points) ・40 points (Input: 24 points,... More Details >>
- No:39340
- Release Date:2023/02/14 17:28
- Category: MELSEC iQ-F Series , CPU Module
-
Regarding the possibility of adding an additional module to the FX5S CPU module
You cannot. The FX5S CPU module does not support the connection of an additional module (I/O module, Intelligent function module, FX5 safety extension modul... More Details >>
- No:39339
- Release Date:2023/02/14 17:28
- Category: MELSEC iQ-F Series , CPU Module
-
Regarding the number of expansion adapters and expansion board connections for FX5S CPU module
Up to 6 devices can be connected. Extension adapters/boards (Max. 2 units) + analog extension adapters (Max. 4 units). *Using an SD memory card module ... More Details >>
- No:39336
- Release Date:2023/02/14 17:13
- Category: MELSEC iQ-F Series , CPU Module
-
It is not possible to convert to GX Works2 format. More Details >>
- No:39326
- Release Date:2023/02/14 09:03
- Category: MELSEC iQ-F Series , CPU Module , Engineering Software
-
Regarding device comment output to Data Logging Files
Device comments can not be output to data logging files. More Details >>
- No:39321
- Release Date:2023/02/14 09:00
- Category: MELSEC iQ-F Series , CPU Module
-
Regarding the COM terminal of the multiple input module
Yes, it's connected internally. More Details >>
- No:39318
- Release Date:2023/01/12 16:54
- Category: MELSEC iQ-F Series , Analog
-
Regarding the input circuit wiring of the FX5 CPU module
Yes. There is no problem using an external power supply for the input circuit of the FX5 CPU module. More Details >>
- No:39317
- Release Date:2023/02/14 08:56
- Category: MELSEC iQ-F Series , CPU Module