FAQ


FAQAbout Products
FAQ
Keyword Search
Controllers
FAQ within [ Controllers ]
-
Inputting device comments in GX Works2
Select [Tool] -> [Options] -> [Program Editor] -> "Ladder/SFC"-> "Comment" and change "Reference/Reflection Target for Device Comment" from "Glob... More Details >>
- No:22559
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
Torque is limited by the lower set value of "[Pr.17] Torque limit setting value" and "[Cd.22] New torque value/forward new torque value".When the current tor... More Details >>
-
Regarding how to format an SD memory card
In GX Works3, go to Online > CPU Memory Operation, select "SD Memory Card" and execute "Initialization." More Details >>
- No:39344
- Release Date:2023/02/15 10:03
- Category: MELSEC iQ-F Series , Option , CPU Module , Engineering Software
-
How to change the keeping (latched device data) range (FX3G/FX3GC)
The keeping (latched device data) range is fixed and cannot be changed in parameters. (Reference) [When an optional battery is not used] The keeping ran... More Details >>
- No:22260
- Release Date:2018/08/30 13:48
- Update:2019/02/19 11:52
- Category: MELSEC-F Series , Engineering Software , Main Unit , Accessories
-
Regarding simulation function using GX Works3
For FX5U/FX5UC CPU modules, GX Works3 Ver. 1.025B or later is supported, and for FX5UJ CPU modules, GX Works3 Ver. 1.065T or later is supported. FX5S CPU mo... More Details >>
- No:22327
- Release Date:2018/08/30 13:55
- Update:2023/02/15 12:56
- Category: MELSEC iQ-F Series , CPU Module , Engineering Software
-
Set "[PA04] Function selection A-1" to "_1_ _h: Invalid".(Note): When using Q17nCPUN, set "Servo amplifier parameter 23 (Optional function 1)"... More Details >>
-
Check if 24 VDC power is supplied to "1A7" (pin No.) of the external input signal connector. More Details >>
-
How to check the scan time (MELSEC-F series)
The present scan time is stored in D8010. Monitor the valueusing a programming tool such as GX Works2 and GX Developer. More Details >>
- No:24685
- Release Date:2019/02/22 11:40
- Update:2019/02/22 15:07
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
Regarding how to clear simple CPU communication function errors
After removing the error factor, you can clear it by executing "Clear latest error code" from "Diagnostic" - "Simple CPU Communication Diagnostic" in GX Work... More Details >>
- No:40049
- Release Date:2023/08/25 09:06
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication
-
How to reset M8004 (Error occurrence)
Yes, it is. However, if the error cause is not eliminated, M8004 will turn on again after powering on. * How to check the error In the FX3S/FX3G/FX3GC/FX... More Details >>
- No:22280
- Release Date:2018/08/30 13:48
- Category: MELSEC-F Series , Engineering Software , Main Unit
971-980 of Total 1123