Error 3012 occurs when the multiple CPU setting of PLC CPU (CPU No.1) does not match that of Motion CPU. (1) Check if the multiple CPU setting of the Multipl... More Details >>
-
Yes. You can check the servo status through the following monitor data. • "[Md.108] Servo status 1" • "[Md.119] Servo status 2" • "[Md.125] Servo status 3... More Details >>
-
Check the following signals. • Start accept flag (M2001 to M2032) • Positioning start complete signal (M4000+20n (n: Axis No.-1)) More Details >>
-
Warning 093CH (Home position return data incorrect) occurs when the backup data for absolute position restoration is lost.Execute the machine home position r... More Details >>
-
Acceleration/deceleration time change
No, the time cannot be changed during operation. (Note): The following is the modules that support the acceleration/deceleration change function. • Q17nDSCP... More Details >>
-
Specify the target axes during operation, and execute the following speed change request instruction. (1) Motion SFC program Speed change request CHGV, CHGVS... More Details >>
-
Minor error 197AH (Home position return zero not passed) occurs in the following case:"[St.1066] zero pass" is OFF when the re-movement to the home position ... More Details >>
- No:23560
- Release Date:2018/09/14 15:09
- Category: RnMTCPU
-
Because the rapid stop deceleration time is larger than the deceleration time.Set the rapid stop deceleration time within the range of 1 to the deceleration ... More Details >>
-
Set "[Pr.45] Home position address" of the basic parameters for home position return • Axis 1 to 16: 72+150n, 73+150n • Axis 17 to 32: 1000072+150n, 1000073+... More Details >>
-
The following shows the initialization procedure. (1) Turn OFF the PLC ready flag. (2) Turn ON "[Cd.2] Parameter initialization request". Set "1" to the buff... More Details >>