FAQ
FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC-F Series
FAQ
Keyword Search
FAQ within [ MELSEC-F Series ]
-
Modules that support differential line driver outputs
The FX3U-2HSY-ADP, FX2N-10PG support differential line driver outputs. More Details >>
- No:24691
- Release Date:2019/02/27 08:56
- Update:2023/02/15 13:09
- Category: MELSEC-F Series , Positioning Control
-
Using the FX3U-ENET-ADP and the RS-232C/RS-485 together (FX3U/FX3UC series)
Up to two of the following optional communication equipment, including the FX3U-ENET-ADP (for Ethernet communications), can be used for the FX3U/FX3UC series... More Details >>
- No:24686
- Release Date:2019/02/22 11:40
- Update:2019/02/22 15:16
- Category: MELSEC-F Series , Main Unit , Network/Communication
-
Ethernet-connectable modules in MELSEC-F
The FX3U-ENET-L and FX3U-ENET-ADP are Ethernet-connectable. The FX3U-ENET-L can be used with the FX3U and FX3UC series (both Ver. 2.21 or later). The FX3U-... More Details >>
- No:22270
- Release Date:2018/08/30 13:48
- Category: MELSEC-F Series , Main Unit , Network/Communication
-
The power supply lamp of a running programmable controller suddenly turned off or flashes
Check whether the lamp is back to normalafter disconnecting the wiring of the "24V" (service power supply) terminal. Ifthe lamp is back to normal,the servic... More Details >>
- No:22267
- Release Date:2018/08/30 13:48
- Update:2019/02/19 11:53
- Category: MELSEC-F Series , Main Unit
-
Parameter setting of the FX3U-16CCL-M
The parameters can be set by using network parameters of GX Works2 (Ver1.73B or later). (FX3U/3UC: Ver3.10 or later) More Details >>
- No:25013
- Release Date:2019/04/23 11:16
- Category: MELSEC-F Series , Engineering Software , Network/Communication
-
Connecting a DC power supply type extension unit to an AC power supply type main unit
No, they cannot be connected. Connect the units having the same power supply type. More Details >>
- No:25008
- Release Date:2019/04/23 11:12
- Category: MELSEC-F Series , Main Unit
-
FX series products that support CC-Link Ver.2.0
FX3U-16CCL-M CC-Link master block and the FX3U-64CCL CC-Link interface block supports CC-Link Ver.2.0. Both blocks are dedicated for the FX3 series. More Details >>
- No:25004
- Release Date:2019/04/23 11:11
- Category: MELSEC-F Series , Network/Communication
-
Index modifier of the bit device in the FX3GC series
FX3GC series does not support the index modifier for the bit devices. FX3U/FX3UC series supports it. More Details >>
- No:25002
- Release Date:2019/04/23 10:39
- Category: MELSEC-F Series
-
Remote maintenance can be performed by writing a program to a memory cassette and sending the program or by using a personal computer (GX Developer). With a ... More Details >>
- No:24998
- Release Date:2019/04/23 10:38
- Category: MELSEC-F Series , Main Unit
-
Temperature input modules that can be used with FX3G series
FX3U-4AD-PT-ADP (Pt100 temperature sensor input special adapter), FX3U-4AD-PTW-ADP (Pt100 temperature sensor input special adapter), and FX3U-4AD-TC-ADP (K/J... More Details >>
- No:24993
- Release Date:2019/04/23 10:38
- Category: MELSEC-F Series , Analog Control
131-140 of Total 198