Set "[Pr.3] Movement amount per rotation" to "36000000(360.00000degree)", and "[Pr.4] Unit magnification" to "1".The same result is obtained by setting "3600... More Details >>
-
Yes. You can check the servo status through the following monitor data. • "[Md.108] Servo status 1" • "[Md.119] Servo status 2" • "[Md.125] Servo status 3... More Details >>
-
Set "[Cd.16] Inching movement amount", and turn ON the Forward run JOG start signal or the Reverse run JOG start signal. More Details >>
-
Refer to "b2: Command in-position flag" of "[Md.31] Status". More Details >>
-
Set "[PA04] Function selection A-1" to "_1_ _h: Invalid". More Details >>
-
Error 093EH (SSCNET communication error) occurs when erroneous data is received from servo amplifier. [When the servo parameter "[PA14] Rotation direction s... More Details >>
-
Error 2035 (Command frequency error) occurs when the servo amplifier detects a command frequency error. (1) When the command from the controller is the permi... More Details >>
-
Because the rapid stop deceleration time is larger than the deceleration time.Set the rapid stop deceleration time within the range of 1 to the deceleration ... More Details >>
- No:23551
- Release Date:2018/09/14 15:09
- Category: RnMTCPU
-
Change the direction with "[PA14] Rotation direction selection/travel direction selection". More Details >>
-
Major error 093CH occurs when the absolute position is erased.Execute the home position return after checking the batteries of the Motion CPU module and the ... More Details >>