No, execute "[Cd.5] Axis error reset" to cancel the error after eliminating the error cause. More Details >>
Linear and circular interpolation
No. To execute continuous positioning and continuous trajectory control, the same target axes and the same number of control axes must be specified in the po... More Details >>
Set the torque limit value in "[Cd.101] Torque output setting value" before the positioning start.The values of "[Pr.17] Torque limit setting value" and "[Cd... More Details >>
There are two ways to start a positioning operation: (1) Set the "[Cd.3] Positioning start No.", and turn ON the positioning start signal. (2) Use the dedica... More Details >>
Check if 24 VDC power is supplied to "1A7" (pin No.) of the external input signal connector. More Details >>
Refer to "b2: Command in-position flag" of "[Md.31] Status". More Details >>
Speed change during JOG operation
Yes. The speed can be changed during JOG operation.Set the new speed with "[Cd.14] New speed value", and then set "[Cd.15] Speed change request" to "1". More Details >>
Alarm E7 (Controller forced stop warning) occurs when an forced stop is executed by the Positioning module or the Simple Motion module. The following shows h... More Details >>
No. The motors' operation is not completely linked to ON/OFF timing of the BUSY signals.BUSY signal is turned ON when the controller starts sending commands ... More Details >>
The BUSY signal turns ON even when position control of movement amount "0" is executed.However, since the ON time is short, the ON status may not be detected... More Details >>