Simple Motion Modules
FAQ within [ Simple Motion Modules ]
-
No. The motors' operation is not completely linked to ON/OFF timing of the BUSY signals.BUSY signal is turned ON when the controller starts sending commands ... More Details >>
-
Set "[Pr.45] Home position address (72+150n, 73+150n)" of the basic parameters for home position return.Set by 2 words.The value will be reflected when PLC r... More Details >>
-
Speed change during JOG operation
Yes. The speed can be changed during JOG operation.Set the new speed with "[Cd.14] New speed value", and then set "[Cd.15] Speed change request" to "1". More Details >>
-
Yes. You can check the servo status through the following monitor data. • "[Md.108] Servo status 1" • "[Md.125] Servo status 3" (QD77MS, LD77MS, LD77MH) ... More Details >>
-
Set "[Cd.17] JOG speed" before starting the operation.When changing the speed during the operation, change it to the new speed with the speed change function. More Details >>
-
The torque limit value can be changed regardless of JOG operation status.Set the new torque limit value with "[Cd.22] New torque value/forward new torque val... More Details >>
-
Error 1205 (SSCNET communication error) occurs when erroneous data is received from servo amplifier. [When the servo parameter "[PA14] Rotation direction se... More Details >>
-
Error 2035 (Command frequency error) occurs when the servo amplifier detects a command frequency error. (1) When the command from the controller is the permi... More Details >>
-
The following shows the initialization procedure. (1) Turn OFF the PLC ready flag. (2) Turn ON "[Cd.2] Parameter initialization request". [QD75M, QD75MH, LD... More Details >>
-
It depends on the setting of servo parameter "[PA03] Absolute position detection system" whether the HPR request flag ("[Md.31] Status": b3) turns ON or not.... More Details >>
21-30 of Total 33