Error 108 (Start not possible) occurs when a start is requested while a stop signal is ON.Check the "[Md.26] Axis operation status".If "20: Servo amplifier ... More Details >>
-
Alarm E7 (Controller forced stop warning) occurs when an forced stop is executed by the Positioning module or the Simple Motion module. The following shows h... More Details >>
-
Error1201 (HPR data incorrect) occurs when the backup data for absolute position restoration is lost.Execute the machine home position return after checking ... More Details >>
-
"M-code" is outputted to turn ON/OFF machine's solenoids or relays according to the start/end of the positioning operation. The following two modes are sele... More Details >>
-
The following shows the initialization procedure. (1) Turn OFF the PLC ready flag. (2) Turn ON "[Cd.2] Parameter initialization request". [QD75M, QD75MH, LD... More Details >>
-
Set "[Pr.45] Home position address (72+150n, 73+150n)" of the basic parameters for home position return.Set by 2 words.The value will be reflected when PLC r... More Details >>
-
Set the torque limit value in "[Cd.101] Torque output setting value" before the positioning start.The values of "[Pr.17] Torque limit setting value" and "[Cd... More Details >>
-
Set "[Cd.17] JOG speed" before starting the operation.When changing the speed during the operation, change it to the new speed with the speed change function. More Details >>
-
Error 1205 (SSCNET communication error) occurs when erroneous data is received from servo amplifier. [When the servo parameter "[PA14] Rotation direction se... More Details >>
-
There are two ways to start a positioning operation: (1) Set the "[Cd.3] Positioning start No.", and turn ON the positioning start signal. (2) Use the dedica... More Details >>