FAQ


FAQAbout Products
FAQ
Keyword Search
Controllers
FAQ within [ Controllers ]
-
The error code "2110" is "SP.UNIT ERROR.". This error may be caused by one of the following factors. (1) The module that has been specified by a FROM/TO i... More Details >>
- No:22662
- Release Date:2018/09/03 17:29
- Update:2018/09/21 13:48
- Category: MELSEC-Q Series
-
Alarm 2149 (Main circuit OFF warning) occurs when the servo system turns ON with no power supplied to the servo main circuit. Review the condition of servo O... More Details >>
-
Set "[Cd.16] Inching movement amount", and turn ON the Forward run JOG start signal or the Reverse run JOG start signal. More Details >>
-
No, there is no impact on the command speed.However, the actual acceleration/deceleration time are affected by the change. More Details >>
-
File registers "R" use the block switching method. The number of file register points used are divided and specified in units of 32k points. When multiple ... More Details >>
- No:22512
- Release Date:2018/09/03 17:28
- Update:2018/09/20 13:29
- Category: MELSEC-Q Series
-
The error code "2401" is "FILE SET ERROR". The individual information parameter number "1100H" corresponds to a file register. The cause of the error is th... More Details >>
- No:22535
- Release Date:2018/09/03 17:28
- Update:2018/09/20 14:46
- Category: MELSEC-Q Series
-
Regarding the latch settings of data register
It is necessary to set the latch range from the following GX Works3 parameters: [Navigation Window] -> [CPU Parameters] -> [Device/Memory Settings] -&... More Details >>
- No:22329
- Release Date:2018/08/30 13:55
- Update:2024/11/11 13:49
- Category: CPU Module , Engineering Software
-
Set the torque limit value in "[Cd.101] Torque output setting value" before the positioning start.The values of "[Pr.17] Torque limit setting value" and "[Cd... More Details >>
-
The following shows the initialization procedure. (1) Turn OFF the PLC ready flag. (2) Turn ON "[Cd.2] Parameter initialization request". [QD75M, QD75MH, LD... More Details >>
-
Error1201 (HPR data incorrect) occurs when the backup data for absolute position restoration is lost.Execute the machine home position return after checking ... More Details >>