FAQ


FAQAbout Products
FAQ
Keyword Search
Controllers
FAQ within [ Controllers ]
-
Difference in specifications between CC-Link versions
Ver.1.10 is a standard where CC-Link station-to-station cable length restriction in Ver. 1.00 has been removed, and the length of all station-to-station cabl... More Details >>
- No:22975
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Difference between the CC-Link IE Controller Network and a MELSECNET/H network
The CC-Link IE Controller Network is an improved system that has a higher processing speed and a larger data capacity than the MELSECNET/H network system (PL... More Details >>
- No:22979
- Release Date:2018/09/03 17:31
- Update:2018/09/25 17:17
- Category: Network related products
-
CC-Link signals checked when an error occurs
Check the following signals.- Module error signal : X0- Host data link status signal: X1- Other station data link status signal: X3 More Details >>
- No:23021
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Limitation on the number of levels of cascade connections when QJ71E71-100 is used
If a repeater hub is used, 10BASE-T allows a maximum of four levels of cascade connections and 100BASE-TX allows a maximum of two levels of cascade connectio... More Details >>
- No:23040
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Whether or not multiple QJ72LP25-25 modules can be mounted
No, only a single QJ72LP25-25 can be mounted (and is to be mounted on the CPU slot on a main base unit). More Details >>
- No:23042
- Release Date:2018/09/03 17:31
- Category: Network related products
-
To assure 32-bit data, "Network Range Assignment" of the control station must satisfy the following conditions.(1) The start device No. of LB is a multiple o... More Details >>
- No:23052
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Refresh timing of bit data and word data in the same CC-Link station
Cyclic data is sometimes separated into new and old data by two words (32 bits) with auto refresh timing. Checking "Block data assurance per station" of the ... More Details >>
- No:23058
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Assignment for connecting two CC-Link remote input modules (16-point type) (Remote net Ver.1 mode)
X devices will be assigned as follows. (With this setting, 32 points are occupied per station.) - Station No. 1: X100 to X11F -Station No. 2: X120 to X13... More Details >>
- No:23082
- Release Date:2018/09/03 17:31
- Update:2018/09/26 13:15
- Category: Network related products
-
Memory cassettes that can be used in the FX3G series
The FX3G-EEPROM-32L can be used. More Details >>
- No:24953
- Release Date:2019/04/18 14:28
- Category: MELSEC-F Series , Accessories
-
Regarding the input circuit wiring of the FX5 CPU module
Yes. There is no problem using an external power supply for the input circuit of the FX5 CPU module. More Details >>
- No:39317
- Release Date:2023/02/14 08:56
- Category: MELSEC iQ-F Series , CPU Module