Regarding the login screen for the Web Server Function
There is no setting or method to disable the login screen for the web server function. More Details >>
- No:44357
- Release Date:2024/03/27 15:52
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication
-
Regarding how to generate a false error
There is no function to generate a false error. For example, if operand (s2): divisor is set to "0" in the division command and the command is executed, err... More Details >>
- No:44610
- Release Date:2024/11/28 16:11
- Category: MELSEC iQ-F Series , CPU Module
-
Regarding how to change the averaging processing of FX5-4AD-ADP programmatically
It is possible to change the number of counts for count averaging in a program. Set the module parameter Basic settings to "Set A/D conversion method" to Di... More Details >>
- No:44618
- Release Date:2024/11/28 16:13
- Category: MELSEC iQ-F Series , Analog
-
Regarding printing of cross-references
If cross-references are displayed on GX Works3, you can print them. More Details >>
- No:44619
- Release Date:2024/11/28 16:10
- Category: MELSEC iQ-F Series , CPU Module , Engineering Software
-
Regarding updating the FX5U/FX5UC CPU module to firmware version “1.100 ” or later
To update to firmware version “1.100 ” or higher, you need a product with serial number (S/N) or higher listed below. ・FX5UC-32MT/DS-TS and FX5UC-32MT/DSS-T... More Details >>
- No:44623
- Release Date:2024/11/28 16:14
- Category: MELSEC iQ-F Series , CPU Module
-
Regarding the method to check the scan time
The current value of the scan time is stored in the following special devices. Please monitor using GX Works3. ◇Scan information SD520 Current scan time (... More Details >>
- No:22289
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:20
- Category: MELSEC iQ-F Series , CPU Module , Engineering Software
-
Regarding the maximum number of channels of high-speed counters
The FX5 CPU module's built-in high-speed counter can control up to 8CH. Up to 16CH can be controlled by adding 4 modules of FX5-16ET/E□-H (high-speed pulse ... More Details >>
- No:22311
- Release Date:2018/08/30 13:55
- Update:2023/02/13 15:34
- Category: MELSEC iQ-F Series , CPU Module , High-Speed Counter
-
Regarding expansion of communication ports
It is possible to use the MODBUS serial communication with multiple channels. However, only 1 channel can be set as the master. The MODBUS serial communica... More Details >>
- No:22323
- Release Date:2018/08/30 13:55
- Update:2023/06/26 09:04
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication
-
Regarding model name of CC-Link cables
The CC‐Link cables are being produced by various manufacturers, and no specific cable model is recommended. Please use a cable certified by the CC-Link Asso... More Details >>
- No:22330
- Release Date:2018/08/30 13:55
- Update:2023/07/03 11:53
- Category: MELSEC iQ-F Series , Network/Communication
-
How to use the database function of the MELSEC iQ-R series
The database function manages tabular data including product information and production information as a database in a programmable controller. <... More Details >>
- No:22476
- Release Date:2018/09/03 17:28
- Update:2018/09/19 14:44
- Category: MELSEC iQ-R Series