Built-in variable analog potentiometers of the FX3G series
D8030 for VR1, and D8031 for VR2. More Details >>
- No:24769
- Release Date:2019/02/27 15:01
- Category: MELSEC-F Series , Main Unit , Analog Control
-
Assignment of remote input device and remote output device of FX3U-16CCL-M
The remote input device and the remote output device cannot be assigned in network parameters. To assign them, create a program for updating data. For de... More Details >>
- No:24792
- Release Date:2019/02/28 09:08
- Category: MELSEC-F Series , Engineering Software , Network/Communication
-
Using a fixed latched (battery backed) type device as a general type device
Clear the required area with the ZRST instruction by using the initial pulse when the programmable controller is set to RUN. To clear all the latched type de... More Details >>
- No:24925
- Release Date:2019/04/17 11:42
- Category: MELSEC-F Series , Main Unit
-
Network No., Group No., and Station No. in Network Parameter
- Network No. is a number assigned to identify each network when multiple networks are configured. Each network No. must be unique. - Group No. is a num... More Details >>
- No:22550
- Release Date:2018/09/03 17:28
- Update:2018/09/20 15:48
- Category: MELSEC-Q Series
-
Alive check for built-in Ethernet port LCPU
When the protocol is set to TCP, KeepAlive check is performed. (Checking for a response to KeepAlive ACK message) An alive check message is sent five seconds... More Details >>
- No:22782
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
SNTP communication error in built-in Ethernet port LCPU
The error does not affect the CPU time. The CPU time is not set when a communication error occurs. More Details >>
- No:22783
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Models from the FX programmable controllers that support the extended register (R)
The following models from the FX3 series support the extended register (R). FX3U/FX3UC series: R0-R32767, FX3G series: R0-R23999 More Details >>
- No:24904
- Release Date:2019/04/15 11:31
- Category: MELSEC-F Series , Main Unit
-
Operation error of the instruction that handles the present value of a high-speed counter
The present value register of the high-speed counter is the 32-bit register. The applied instruction handling the 32-bit register must be the 32-bit instruct... More Details >>
- No:24907
- Release Date:2019/04/15 11:32
- Category: MELSEC-F Series , High-Speed Counting
-
Switching network between 10BASE-T and 100BASE-TX of the FX3U-ENET-L
It cannot be freely switched. It is automatically switched according to the auto detection function. More Details >>
- No:24964
- Release Date:2019/04/23 07:18
- Category: MELSEC-F Series , Network/Communication
-
Operation of the first special function unit/block in the FX3UC series
Usually, unit number of the first special function unit/block is "K0". However, when the main unit is FX3UC-32MT-LT(-LT2), the unit number "K0" is assigned t... More Details >>
- No:24995
- Release Date:2019/04/23 10:40
- Category: MELSEC-F Series , Main Unit