FAQ


FAQAbout Products
FAQ
Keyword Search
Controllers
FAQ within [ Controllers ]
-
Regarding the type of Ethernet connection cable
Ethernet standard-compatible cable, category 5 or higher (STP cable) can be used. *Straight cable can be used. When connecting directly to the computer, cr... More Details >>
- No:22295
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:23
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication
-
The FX3 intelligent function modules cannot be selected from the Element selection window because it does not correspond to the parameter setting of GX Works... More Details >>
- No:22304
- Release Date:2018/08/30 13:55
- Update:2024/08/19 09:50
- Category: MELSEC iQ-F Series , CPU Module , Engineering Software
-
Regarding the frequency of high-speed counters
The maximum frequency of the FX5U/FX5UC CPU module is 200kHz and the maximum frequency of the FX5S/FX5UJ CPU module is 100 kHz. More Details >>
- No:22312
- Release Date:2018/08/30 13:55
- Update:2022/12/22 10:18
- Category: MELSEC iQ-F Series , CPU Module , High-Speed Counter
-
Regarding the specifications of the built-in Ethernet function of FX5 CPU module
The connection using the Ethernet port can establish a total of 8 connections which includes SLMP, MELSOFT connection, MODBUS/TCP, socket communication, and ... More Details >>
- No:22320
- Release Date:2018/08/30 13:55
- Update:2023/07/04 15:52
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication
-
Grounding FG and LG terminals of power supply module
Both of them need to be grounded. They can be shorted and grounded as one cable. More Details >>
- No:22527
- Release Date:2018/09/03 17:28
- Category: MELSEC-Q Series
-
SD520 stores the current scan time in 1 ms units. More Details >>
- No:22556
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
NTP support by the SNTP function of LCPU with built-in Ethernet port
NTP and SNTP are compatible. Therefore, an NTP server can be used for clock setting. More Details >>
- No:22744
- Release Date:2018/09/03 17:29
- Category: MELSEC-L Series
-
The error code "2110" is "SP.UNIT ERROR.". This error may be caused by one of the following factors.(1) The module that has been specified by a FROM/TO instr... More Details >>
- No:22830
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Terminating resistors for RS-485 communication of QJ71C24N
The resistance value is 110 ohm, 1/2 W. More Details >>
- No:22978
- Release Date:2018/09/03 17:31
- Update:2018/10/03 15:48
- Category: Network related products
-
What makes the ERR LED flash in a CC-Link network
A link error has occurred in one of the slave stations in connection.Master station: Check the parameter again.Slave station: Reassess the power supply, the ... More Details >>
- No:23023
- Release Date:2018/09/03 17:31
- Category: Network related products
851-860 of Total 1123