Set "[PA04] Function selection A-1" to "_1_ _h: Invalid".(Note): When using Q17nCPUN, set "Servo amplifier parameter 23 (Optional function 1)"... More Details >>
-
Servo motor rotation direction
To reflect the change, set "[PA14] Rotation direction selection/traveldirection selection" and cycle the servo amplifier or execute a home position return af... More Details >>
-
M384 to M1535 and D128 to D1099 can be latched. M1536 to M7679, D1100 to D7999, and R0 to R23999 can be used as latch areas by installing an optional batt... More Details >>
- No:24703
- Release Date:2019/02/27 08:59
- Category: MELSEC-F Series , Engineering Software , Main Unit , Accessories
-
How to change the keeping (latched device data) range (FX3G/FX3GC)
The keeping (latched device data) range is fixed and cannot be changed in parameters. (Reference) [When an optional battery is not used] The keeping ran... More Details >>
- No:22260
- Release Date:2018/08/30 13:48
- Update:2019/02/19 11:52
- Category: MELSEC-F Series , Engineering Software , Main Unit , Accessories
-
How to read the device memory in GX Works2
Select [Online] -> [Read from PLC] from the menu and check "Device Memory" in the file list in the window and then execute PLC read. More Details >>
- No:22621
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
The error code "2200" is "MISSING PARA.". The causes of the error are described below. (1) The necessary parameter file does not exist in all drives. (2) ... More Details >>
- No:22749
- Release Date:2018/09/03 17:29
- Update:2018/09/22 09:12
- Category: MELSEC-L Series
-
Differences between CC-Link IE Control Network and CC-Link IE Field Network
The CC-Link IE Control Network is a high-capacity controller network whose maximum number of link points is 128k words. The CC-Link IE Field Network is an al... More Details >>
- No:23085
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Resistor value for CC-Link cables
The value depends on the type of cable in use. - Ver.1.10-compatible CC-Link dedicated cables: 110 ohm, 1/2W - CC-Link dedicated cables (Version 1.00): 110... More Details >>
- No:22983
- Release Date:2018/09/03 17:31
- Update:2018/10/03 14:42
- Category: Network related products
-
Speed limit value change during operation
No, the speed limit cannot be changed during operation. More Details >>
-
Yes. You can check the servo status through the following monitor data. • "[Md.108] Servo status 1" • "[Md.125] Servo status 3" (QD77MS, LD77MS, LD77MH) ... More Details >>