FAQ


FAQAbout Products

- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC-F Series
FAQ
Keyword Search
FAQ within [ MELSEC-F Series ]
-
Connection of a totem pole output encoder
The totem pole output encoder cannot be connected to the FX2NC-1HC/FX2N-1HC/ FX3U-2HC. The connectable encoders are as follows. ・ Open collector output typ... More Details >>
- No:25010
- Release Date:2019/04/23 11:12
- Category: MELSEC-F Series , High-Speed Counting
-
Whether the positioning parameter is used or the extension positioning parameter is used can be selected in BFM#32 (positioning parameter selection). Select ... More Details >>
- No:24917
- Release Date:2019/04/17 11:40
- Category: MELSEC-F Series , Positioning Control
-
Use of latched (battery backed) type auxiliary relay
If the OUT instruction using a latched (battery backed) type auxiliary relay number exists in a sequence program, the information held may be overwritten by ... More Details >>
- No:24877
- Release Date:2019/04/15 08:07
- Category: MELSEC-F Series , Main Unit
-
Output numbers of the FX programmable controllers
Since they are octal, the number after Y7 is Y10 and after Y77 is Y100. More Details >>
- No:24946
- Release Date:2019/04/18 14:26
- Category: MELSEC-F Series
-
How to use built-in high-speed counters
For contacts to drive the coils of high-speed counters, use the contacts which are normally on during high-speed counting. Do not use the input (X000 to X00... More Details >>
- No:24684
- Release Date:2019/02/22 11:38
- Update:2019/02/22 15:03
- Category: MELSEC-F Series , High-Speed Counting
-
Connecting a DC power supply type extension unit to an AC power supply type main unit
No, they cannot be connected. Connect the units having the same power supply type. More Details >>
- No:25008
- Release Date:2019/04/23 11:12
- Category: MELSEC-F Series , Main Unit
-
Number of FX3U-64CCL interface blocks that can be added to a main unit
One FX3U-64CCL can be added. More Details >>
- No:24962
- Release Date:2019/04/23 07:17
- Category: MELSEC-F Series , Network/Communication
-
It takes 1 ms or less in a unit of the motor system and 2 ms or less in a unit of the machine system. * Motor system∙∙∙The pulse number is used as the stand... More Details >>
- No:24943
- Release Date:2019/04/18 14:25
- Category: MELSEC-F Series , Positioning Control
-
The thickness of wireshould be2 square millimeters or more, andclass D grounding (grounding resistance: 100 Ω or less) should be performed. More Details >>
- No:24899
- Release Date:2019/04/15 11:30
- Category: MELSEC-F Series , Main Unit
-
MC protocol supported by the FX3U-ENET-L
The frame typesupported byMC protocol is equivalent to A-compatible 1E frame. More Details >>
- No:24702
- Release Date:2019/02/27 08:59
- Category: MELSEC-F Series , Network/Communication
141-150 of Total 198