FAQ


FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC-F Series
FAQ
Keyword Search
FAQ within [ MELSEC-F Series ]
-
Externally switching the operating status of a programmable controller
On the Project view of the Navigation window, select "Parameter" → "PLC Parameter" using GX Works2 (or GX Developer). Click the "PLC System(1)" tab, and set ... More Details >>
- No:24768
- Release Date:2019/02/27 15:01
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
Built-in variable analog potentiometers of the FX3G series
D8030 for VR1, and D8031 for VR2. More Details >>
- No:24769
- Release Date:2019/02/27 15:01
- Category: MELSEC-F Series , Main Unit , Analog Control
-
Differences between the FX3UC-32MT-LT and the FX3UC-32MT-LT2
The built-in CC-Link/LT setting differs. For the FX3UC-32MT-LT, the built-in CC-Link/LT setting is performed with the DIP switch. For the FX3UC-32MT-LT2, th... More Details >>
- No:24956
- Release Date:2019/04/18 14:28
- Category: MELSEC-F Series , Main Unit , Network/Communication
-
Operation processing time of the programmable controller
The constant operation processing time can be achieved by using constant scan mode. Refer to the programming manual of the programmable controller used. More Details >>
- No:24997
- Release Date:2019/04/23 10:38
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
I/O structure error in the MELSEC-F
When an unimplemented input (X) or output (Y) number is used in a program, M8060 turns on. The first to third digits of the numericalvalue stored in D8060 i... More Details >>
- No:22284
- Release Date:2018/08/30 13:48
- Update:2019/02/18 15:17
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
Ver.3.10 or later is applicable. (GX Works2 with Ver.1.73B or later is applicable.) The version of the main unit can be checked with the last three digits of... More Details >>
- No:24918
- Release Date:2019/04/17 11:40
- Category: MELSEC-F Series , Main Unit
-
All input COM terminals send the same signal because all the terminals are internally connected. To turn on the input, the extension unit must be connected ... More Details >>
- No:22274
- Release Date:2018/08/30 13:48
- Category: MELSEC-F Series , Main Unit , I/O Extension
-
To establish communications between the programmable controller and GX Developer, clear the communication setting. (The communication setting register value ... More Details >>
- No:24876
- Release Date:2019/04/15 08:07
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
Measurement of the counter in the MC (master control) circuit
When the count condition of the counter in the MC circuit remains set, the counter counts when the MC circuit is turned on. More Details >>
- No:24910
- Release Date:2019/04/15 11:32
- Category: MELSEC-F Series , Main Unit
-
Maximum number of personal computers that can be communicated with the FX3U-ENET-L simultaneously
For communications using MELSOFT connection, such as GX Developer, GX Works2, GOT1000, and MX Component, up to two personal computers can be used. In additi... More Details >>
- No:24920
- Release Date:2019/04/17 11:41
- Category: MELSEC-F Series , Network/Communication
151-160 of Total 198