Meanings of the sink input/source input
The sink input connects to a negative common for 24 V DC. The source input connects to a positive common. The sink input is generally used in Japan and No... More Details >>
- No:22254
- Release Date:2018/08/30 13:48
- Category: MELSEC-F Series , Main Unit , I/O Extension
-
Types of data backup methods (FX3G series)
1. Data backup using an optional battery Built-in RAM data and clock data of a programmable controller are held by using an optional battery. The life of... More Details >>
- No:24701
- Release Date:2019/02/27 08:59
- Category: MELSEC-F Series , Engineering Software , Main Unit , Accessories
-
Keyword protection of the MELSEC-F series
The keyword protection cannot be forcibly reset. Since only the keyword that has been registered by theuser is acceptable, please take measures to ensure th... More Details >>
- No:24784
- Release Date:2019/02/27 16:27
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
How to reset M8004 (Error occurrence)
Yes, it is. However, if the error cause is not eliminated, M8004 will turn on again after powering on. * How to check the error In the FX3S/FX3G/FX3GC/FX... More Details >>
- No:22280
- Release Date:2018/08/30 13:48
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
How to change the keeping (latched device data) range (FX3G/FX3GC)
The keeping (latched device data) range is fixed and cannot be changed in parameters. (Reference) [When an optional battery is not used] The keeping ran... More Details >>
- No:22260
- Release Date:2018/08/30 13:48
- Update:2019/02/19 11:52
- Category: MELSEC-F Series , Engineering Software , Main Unit , Accessories
-
Using a specified bit (on/off) of a word device (D) as a condition for a contact
In the FX3U/FX3UC series, a bit in a word device can be specified. It can be specified by "Word device (D only) + Decimal point + Bit position (0 to F)". A... More Details >>
- No:22261
- Release Date:2018/08/30 13:48
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
Latch (backup) areas in the data register (D) and extended register (R) of the FX3U/FX3UC series
D200 to D7999 and R0 to R32767 can be latched. D200 to D511 can be set as non-latch areas in parameters. For details on the parameter setting, refer to the... More Details >>
- No:24699
- Release Date:2019/02/27 08:58
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
Thecomment may not have been written tothe programmable controller. Or, the comment display setting may be required on the GX Works2 side. [Writing a com... More Details >>
- No:24681
- Release Date:2019/02/22 11:40
- Update:2019/02/22 14:15
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
M8029 (Instruction execution complete flag) is shared with multiple instructions. To obtain an execution completion result of a specific instruction, insert... More Details >>
- No:24775
- Release Date:2019/02/27 15:34
- Category: MELSEC-F Series , Network related products , Main Unit
-
Compliance of the FX programmable controllers with the EU RoHS Directive
Most of the existing programmable controllers are compliant with the EU RoHS Directive. For details, please consult your local Mitsubishi Electric representa... More Details >>
- No:24888
- Release Date:2019/04/15 08:07
- Category: MELSEC-F Series , Main Unit , I/O Extension , Analog Control , High-Speed Counting , Positioning Control , Network/Communication , Accessories