FAQ


FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC-F Series
FAQ
Keyword Search
FAQ within [ MELSEC-F Series ]
-
Changing the time of a programmable controller by using the clock data write instruction (TWR)
When changing the time by using the clock data write instruction (TWR), the control of M8015 (Clock stop/adjustment) is not required. * When the clock data... More Details >>
- No:22266
- Release Date:2018/08/30 13:48
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
Differences between the file register and other registers
The file register is used for storing predetermined values (such as specification values for product inspection). Other registers are used as a temporary st... More Details >>
- No:22256
- Release Date:2018/08/30 13:48
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
Counting of a built-in high-speed counter
Check that the RST instruction ofthe high-speed counter is not executed whilethe program is running. Forthe high-speed counter which supports the external r... More Details >>
- No:24787
- Release Date:2019/02/28 09:06
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
Latched (battery backed) area in the data register (D) of the FX3G/FX3GC series
D128 to D1099 are the latched device area. D1100 to D7999 can be changed to latched (battery backed) type devices by installing an optional battery and setti... More Details >>
- No:24901
- Release Date:2019/04/15 11:31
- Category: MELSEC-F Series , Main Unit
-
How to check the scan time (MELSEC-F series)
The present scan time is stored in D8010. Monitor the valueusing a programming tool such as GX Works2 and GX Developer. More Details >>
- No:24685
- Release Date:2019/02/22 11:40
- Update:2019/02/22 15:07
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
Connection of the FX3G series and the FX3U-ENET-ADP
AnFX3G-CNV-ADP is required. * When the FX3U-ENET-ADP is used with other special adapters, connect the FX3U-ENET-ADP at the last stage (left end). More Details >>
- No:24951
- Release Date:2019/04/18 14:27
- Category: MELSEC-F Series , Main Unit
-
How to reset M8004 (Error occurrence)
Yes, it is. However, if the error cause is not eliminated, M8004 will turn on again after powering on. * How to check the error In the FX3S/FX3G/FX3GC/FX... More Details >>
- No:22280
- Release Date:2018/08/30 13:48
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
If the OUT instruction using the device number of the latch target device exists in a sequence program, the latched data may be overwritten by execution of t... More Details >>
- No:24783
- Release Date:2019/02/27 16:16
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
Communication setting methods when the FX3U-232-BD is used
The non-protocol communication can be set by the following two methods: (1) setting parameters using a programming tool, such as GX Works2, or (2) writing da... More Details >>
- No:24773
- Release Date:2019/02/27 15:24
- Category: MELSEC-F Series , Engineering Software , Network/Communication
-
Turning on a bit in the data register
In the FX3U/FX3UC series, the bit specification of the data register is possible. (Example) D0.7→7th bit in D0 For the other types of MELSEC-F programmable... More Details >>
- No:22275
- Release Date:2018/08/30 13:48
- Category: MELSEC-F Series , Engineering Software , Main Unit