FAQ within [ Main Unit ]
-
Number of occupied points of special function devices
Each special function unit/block has 8 occupied points, except for some special function devices. These 8 points do not occupy 8 points of the actual I/O n... More Details >>
- No:24873
- Release Date:2019/04/15 08:06
-
Terminal blocks for the MELSEC-F series
Whether the terminal block is removable or not differs depending on the series. Types of the terminal blocks for the MELSEC-F series main units are as follow... More Details >>
- No:24774
- Release Date:2019/02/27 15:34
-
Connection of expansion boards and a display module to FX3G series main unit
They can be used together. * 14/24-point type FX3G series main unit ・ An expansion board can be connected to BD1 (1st position) and a display module can be... More Details >>
- No:24985
- Release Date:2019/04/23 07:22
-
CF cards that can be used in the FX3U-CF-ADP
The CF cards, whose operations are guaranteed, are the following five models manufactured by Mitsubishi Electric. GT05-MEM-128MC, GT05-MEM-256MC, GT05-MEM-5... More Details >>
- No:24945
- Release Date:2019/04/18 14:26
-
Clock function accuracy of the MELSEC-F series
The accuracy is within ±45 seconds/month (ambient temperature: 25ºC). More Details >>
- No:24778
- Release Date:2019/02/27 15:57
-
Terminal layout on the output side of the FX3U-16MR/ES
Yes, they are independent common terminals. More Details >>
- No:24955
- Release Date:2019/04/18 14:23
-
Remote maintenance can be performed by writing a program to a memory cassette and sending the program or by using a personal computer (GX Developer). With a ... More Details >>
- No:24998
- Release Date:2019/04/23 10:38
-
Connection of the FX3GC series and FX3U-ENET-ADP
Since the FX3U-ENET-ADP can be connected directly to the FX3GC series, optional equipment is not required. * When the FX3U-ENET-ADP is used with other spe... More Details >>
- No:24976
- Release Date:2019/04/23 07:20
-
Overwriting a current value with the high-speed counter comparison instruction
The output contact is activated according to the change of the current value register along with the counting input. Therefore, the value changed by executin... More Details >>
- No:24931
- Release Date:2019/04/17 11:43
-
AC input type main unit in the FX3 series
FX3U-32MR/UA1 and FX3U-64MR/UA1 are AC input types. More Details >>
- No:24991
- Release Date:2019/04/23 10:37