FAQ


FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC-F Series > Main Unit
FAQ
Keyword Search
FAQ within [ Main Unit ]
-
Latch (backup) areas in the data register (D) and extended register (R) of the FX3U/FX3UC series
D200 to D7999 and R0 to R32767 can be latched. D200 to D511 can be set as non-latch areas in parameters. For details on the parameter setting, refer to the... More Details >>
- No:24699
- Release Date:2019/02/27 08:58
-
M8029 (Instruction execution complete flag) is shared with multiple instructions. To obtain an execution completion result of a specific instruction, insert... More Details >>
- No:24775
- Release Date:2019/02/27 15:34
-
Using a specified bit (on/off) of a word device (D) as a condition for a contact
In the FX3U/FX3UC series, a bit in a word device can be specified. It can be specified by "Word device (D only) + Decimal point + Bit position (0 to F)". A... More Details >>
- No:22261
- Release Date:2018/08/30 13:48
-
How to change the keeping (latched device data) range (FX3G/FX3GC)
The keeping (latched device data) range is fixed and cannot be changed in parameters. (Reference) [When an optional battery is not used] The keeping ran... More Details >>
- No:22260
- Release Date:2018/08/30 13:48
- Update:2019/02/19 11:52
-
Keyword protection of the MELSEC-F series
The keyword protection cannot be forcibly reset. Since only the keyword that has been registered by theuser is acceptable, please take measures to ensure th... More Details >>
- No:24784
- Release Date:2019/02/27 16:27
-
Meanings of the sink input/source input
The sink input connects to a negative common for 24 V DC. The source input connects to a positive common. The sink input is generally used in Japan and No... More Details >>
- No:22254
- Release Date:2018/08/30 13:48
-
How to reset M8004 (Error occurrence)
Yes, it is. However, if the error cause is not eliminated, M8004 will turn on again after powering on. * How to check the error In the FX3S/FX3G/FX3GC/FX... More Details >>
- No:22280
- Release Date:2018/08/30 13:48
-
How to check the version of the MELSEC-F series
To check the version of the MELSEC-F series, connect GX Works2 (personal computer) or HPP to a programmable controller, and monitor the data in D8001. The l... More Details >>
- No:24772
- Release Date:2019/02/27 15:22
-
Types of data backup methods (FX3G series)
1. Data backup using an optional battery Built-in RAM data and clock data of a programmable controller are held by using an optional battery. The life of... More Details >>
- No:24701
- Release Date:2019/02/27 08:59
-
Changing the time of a programmable controller by using the clock data write instruction (TWR)
When changing the time by using the clock data write instruction (TWR), the control of M8015 (Clock stop/adjustment) is not required. * When the clock data... More Details >>
- No:22266
- Release Date:2018/08/30 13:48
11-20 of Total 126