Replacement of the fuse in the FX programmable controller
Customers cannot replace the fuse. For the replacement, please consult your local Mitsubishi representative. More Details >>
- No:24909
- Release Date:2019/04/15 11:30
-
Using a fixed latched (battery backed) type device as a general type device
Clear the required area with the ZRST instruction by using the initial pulse when the programmable controller is set to RUN. To clear all the latched type de... More Details >>
- No:24925
- Release Date:2019/04/17 11:42
-
One FX3U-ENET-ADP can be connected at the last stage (left end) of adapters for the FX3GC series. * The FX3U-ENET-ADP is a communication special adapter and... More Details >>
- No:24967
- Release Date:2019/04/23 07:18
-
Operation processing time of the programmable controller
The constant operation processing time can be achieved by using constant scan mode. Refer to the programming manual of the programmable controller used. More Details >>
- No:24997
- Release Date:2019/04/23 10:38
-
How to change the keeping (latched device data) range (FX3G/FX3GC)
The keeping (latched device data) range is fixed and cannot be changed in parameters. (Reference) [When an optional battery is not used] The keeping ran... More Details >>
- No:22260
- Release Date:2018/08/30 13:48
- Update:2019/02/19 11:52
-
For the sink input, the "S/S" terminal and the "24V" terminal are needed to be short-circuited. More Details >>
- No:22263
- Release Date:2018/08/30 13:48
-
The power supply lamp of a running programmable controller suddenly turned off or flashes
Check whether the lamp is back to normalafter disconnecting the wiring of the "24V" (service power supply) terminal. Ifthe lamp is back to normal,the servic... More Details >>
- No:22267
- Release Date:2018/08/30 13:48
- Update:2019/02/19 11:53
-
Yes, there is. T256 to T319 can be used for the1 ms timer, and T246 to T249 can be used for the 1 ms retentive timer. More Details >>
- No:24680
- Release Date:2019/02/22 11:39
- Update:2019/02/22 14:03
-
If the OUT instruction using the device number of the latch target device exists in a sequence program, the latched data may be overwritten by execution of t... More Details >>
- No:24783
- Release Date:2019/02/27 16:16
-
Measurement of the counter in the MC (master control) circuit
When the count condition of the counter in the MC circuit remains set, the counter counts when the MC circuit is turned on. More Details >>
- No:24910
- Release Date:2019/04/15 11:32