For the sink input, the "S/S" terminal and the "24V" terminal are needed to be short-circuited. More Details >>
- No:22263
- Release Date:2018/08/30 13:48
-
Transferring/editing programs in the previous FX programmable controllers using GX Works2
The earlier series of the FX programmable controllers are compatible with the latest series of the FX programmable controllers. More Details >>
- No:25012
- Release Date:2019/04/23 11:16
-
The main units with Ver.2.00 or later can read and write programs of the FX3 series connected to the intelligent device station and can monitor devices. (GX... More Details >>
- No:24950
- Release Date:2019/04/18 14:27
-
How to check the scan time (MELSEC-F series)
The present scan time is stored in D8010. Monitor the valueusing a programming tool such as GX Works2 and GX Developer. More Details >>
- No:24685
- Release Date:2019/02/22 11:40
- Update:2019/02/22 15:07
-
Built-in variable analog potentiometers of the FX3G series
D8030 for VR1, and D8031 for VR2. More Details >>
- No:24769
- Release Date:2019/02/27 15:01
-
I/O structure error in the MELSEC-F
When an unimplemented input (X) or output (Y) number is used in a program, M8060 turns on. The first to third digits of the numericalvalue stored in D8060 i... More Details >>
- No:22284
- Release Date:2018/08/30 13:48
- Update:2019/02/18 15:17
-
Use of latched (battery backed) type auxiliary relay
If the OUT instruction using a latched (battery backed) type auxiliary relay number exists in a sequence program, the information held may be overwritten by ... More Details >>
- No:24877
- Release Date:2019/04/15 08:07
-
Battery replacement during power-on
Replacethe battery when the programmable controller is powered off. For example, forthe FX3U/FX3UC series, data will be held for about 20 seconds after be... More Details >>
- No:22257
- Release Date:2018/08/30 13:48
- Update:2019/02/19 11:54
-
To establish communications between the programmable controller and GX Developer, clear the communication setting. (The communication setting register value ... More Details >>
- No:24876
- Release Date:2019/04/15 08:07
-
In order for the programmable controller to receive input pulses completely, the ON duration and OFF duration of inputs in the programmable controller requir... More Details >>
- No:24704
- Release Date:2019/02/27 09:00