Connection of expansion boards and a display module to FX3G series main unit
They can be used together. * 14/24-point type FX3G series main unit ・ An expansion board can be connected to BD1 (1st position) and a display module can be... More Details >>
- No:24985
- Release Date:2019/04/23 07:22
-
Connection of a memory cassette and a display module to the FX3G series main unit
For the 14/24-point type FX3G series main unit, they cannot be connected together. For the 40/60-point type FX3G series main unit, they canbe connected toget... More Details >>
- No:24978
- Release Date:2019/04/23 07:20
-
Adding FX3U series expansion boards to an FX3UC series main unit
FX3U series expansion boards can be added to FX3UC-32MT-LT and FX3UC-32MT-LT2. More Details >>
- No:24963
- Release Date:2019/04/23 07:18
-
Overwriting a current value with the high-speed counter comparison instruction
The output contact is activated according to the change of the current value register along with the counting input. Therefore, the value changed by executin... More Details >>
- No:24931
- Release Date:2019/04/17 11:43
-
Replacement of the fuse in the FX programmable controller
Customers cannot replace the fuse. For the replacement, please consult your local Mitsubishi representative. More Details >>
- No:24909
- Release Date:2019/04/15 11:30
-
Number of occupied points of special function devices
Each special function unit/block has 8 occupied points, except for some special function devices. These 8 points do not occupy 8 points of the actual I/O n... More Details >>
- No:24873
- Release Date:2019/04/15 08:06
-
Scan time while operation of a programmable controller CPU is being monitored using GX Works2
Scan time displayed on GX Works2 is the maximum scan time of the monitor target programmable controller CPU. To check current scan time, monitor the data in... More Details >>
- No:24779
- Release Date:2019/02/27 15:58
-
Maximum number of characters in a comment that can be transferred to a FX3U series
As project data, up to 32 one-byte characters (16 two-byte characters) can be input to each global device comment. However, the maximum number of characters ... More Details >>
- No:24700
- Release Date:2019/02/27 08:59
-
I/O structure error in the MELSEC-F
When an unimplemented input (X) or output (Y) number is used in a program, M8060 turns on. The first to third digits of the numericalvalue stored in D8060 i... More Details >>
- No:22284
- Release Date:2018/08/30 13:48
- Update:2019/02/18 15:17
-
All input COM terminals send the same signal because all the terminals are internally connected. To turn on the input, the extension unit must be connected ... More Details >>
- No:22274
- Release Date:2018/08/30 13:48