- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC-F Series > Main Unit
FAQ
Keyword Search
FAQ within [ Main Unit ]
-
How to install a battery to FX3G/FX3GC series
The FX3U-32BL can be installed to the FX3G/FX3GC series. After installation, select [Battery Mode: Use the battery] on the FX parameter window of GX Develop... More Details >>
- No:22271
- Release Date:2018/08/30 13:48
-
Turning on/off a specified bit of a word device (D) using a simple program
In the FX programmable controllers (FX3U/FX3UC series), a bit in a word device can be specified in a program. It can be specified as "word device (D only) + ... More Details >>
- No:25011
- Release Date:2019/04/23 11:13
-
How to change the keeping (latched device data) range (FX3G/FX3GC)
The keeping (latched device data) range is fixed and cannot be changed in parameters. (Reference) [When an optional battery is not used] The keeping ran... More Details >>
- No:22260
- Release Date:2018/08/30 13:48
- Update:2019/02/19 11:52
-
Models from the FX programmable controllers that support the extended register (R)
The following models from the FX3 series support the extended register (R). FX3U/FX3UC series: R0-R32767, FX3G series: R0-R23999 More Details >>
- No:24904
- Release Date:2019/04/15 11:31
-
Latch (backup) areas in the data register (D) and extended register (R) of the FX3U/FX3UC series
D200 to D7999 and R0 to R32767 can be latched. D200 to D511 can be set as non-latch areas in parameters. For details on the parameter setting, refer to the... More Details >>
- No:24699
- Release Date:2019/02/27 08:58
-
M384 to M1535 and D128 to D1099 can be latched. M1536 to M7679, D1100 to D7999, and R0 to R23999 can be used as latch areas by installing an optional batt... More Details >>
- No:24703
- Release Date:2019/02/27 08:59
-
Connecting special adapters to the FX3G series
An FX3G-CNV-ADP is required. More Details >>
- No:24977
- Release Date:2019/04/23 07:20
-
How to check the scan time (MELSEC-F series)
The present scan time is stored in D8010. Monitor the valueusing a programming tool such as GX Works2 and GX Developer. More Details >>
- No:24685
- Release Date:2019/02/22 11:40
- Update:2019/02/22 15:07
-
How to reset M8004 (Error occurrence)
Yes, it is. However, if the error cause is not eliminated, M8004 will turn on again after powering on. * How to check the error In the FX3S/FX3G/FX3GC/FX... More Details >>
- No:22280
- Release Date:2018/08/30 13:48
-
Differences in the specifications between the programmable controllers used in Japan and overseas.
The input signal forms are different. All the programmable controllers for the domestic market other than the FX3G/FX3U series are the sink input. The progra... More Details >>
- No:24913
- Release Date:2019/04/17 11:39