Assignment of input/output numbers (MELSEC-F series)
Octal numbers are assigned as input/output numbers for the MELSEC-F series. The octal number system uses the digits from 0 to 7 → from 10 to 17 → from 20 to... More Details >>
- No:24868
- Release Date:2019/04/15 08:06
-
Model name of a built-in battery (FX3U/FX3UC)
FX3U-32BL More Details >>
- No:22278
- Release Date:2018/08/30 13:48
-
For the sink input, the "S/S" terminal and the "24V" terminal are needed to be short-circuited. More Details >>
- No:22263
- Release Date:2018/08/30 13:48
-
Periodic replacement is recommended. For example, standard life of FX3U-32BL is 5 years (at ambient temperature of 25). The life of the battery changes wit... More Details >>
- No:22262
- Release Date:2018/08/30 13:48
-
Yes, there is. T256 to T319 can be used for the1 ms timer, and T246 to T249 can be used for the 1 ms retentive timer. More Details >>
- No:24680
- Release Date:2019/02/22 11:39
- Update:2019/02/22 14:03
-
Scan time while operation of a programmable controller CPU is being monitored using GX Works2
Scan time displayed on GX Works2 is the maximum scan time of the monitor target programmable controller CPU. To check current scan time, monitor the data in... More Details >>
- No:24779
- Release Date:2019/02/27 15:58
-
In order for the programmable controller to receive input pulses completely, the ON duration and OFF duration of inputs in the programmable controller requir... More Details >>
- No:24704
- Release Date:2019/02/27 09:00
-
To establish communications between the programmable controller and GX Developer, clear the communication setting. (The communication setting register value ... More Details >>
- No:24876
- Release Date:2019/04/15 08:07
-
Battery replacement during power-on
Replacethe battery when the programmable controller is powered off. For example, forthe FX3U/FX3UC series, data will be held for about 20 seconds after be... More Details >>
- No:22257
- Release Date:2018/08/30 13:48
- Update:2019/02/19 11:54
-
All input COM terminals send the same signal because all the terminals are internally connected. To turn on the input, the extension unit must be connected ... More Details >>
- No:22274
- Release Date:2018/08/30 13:48