The "S/S" terminal is used to switch the input type (sink input and source input). For the source input, connect the "S/S" terminal to the "0V" terminal, a... More Details >>
- No:22255
- Release Date:2018/08/30 13:48
-
Deleting all programs and data from the memory
Data can be cleared from GX Developer or GX Works2. [Online]→Select all [PLC memory], [Data device], and [Bit device.] on the Clear PLC memory window, and e... More Details >>
- No:22269
- Release Date:2018/08/30 13:48
-
Latch (backup) areas in the data register (D) and extended register (R) of the FX3U/FX3UC series
D200 to D7999 and R0 to R32767 can be latched. D200 to D511 can be set as non-latch areas in parameters. For details on the parameter setting, refer to the... More Details >>
- No:24699
- Release Date:2019/02/27 08:58
-
M8029 (Instruction execution complete flag) is shared with multiple instructions. To obtain an execution completion result of a specific instruction, insert... More Details >>
- No:24775
- Release Date:2019/02/27 15:34
-
M384 to M1535 and D128 to D1099 can be latched. M1536 to M7679, D1100 to D7999, and R0 to R23999 can be used as latch areas by installing an optional batt... More Details >>
- No:24703
- Release Date:2019/02/27 08:59
-
Changing the time of a programmable controller by using the clock data write instruction (TWR)
When changing the time by using the clock data write instruction (TWR), the control of M8015 (Clock stop/adjustment) is not required. * When the clock data... More Details >>
- No:22266
- Release Date:2018/08/30 13:48
-
Thecomment may not have been written tothe programmable controller. Or, the comment display setting may be required on the GX Works2 side. [Writing a com... More Details >>
- No:24681
- Release Date:2019/02/22 11:40
- Update:2019/02/22 14:15
-
Battery replacement during power-on
Replacethe battery when the programmable controller is powered off. For example, forthe FX3U/FX3UC series, data will be held for about 20 seconds after be... More Details >>
- No:22257
- Release Date:2018/08/30 13:48
- Update:2019/02/19 11:54
-
Ethernet-connectable modules in MELSEC-F
The FX3U-ENET-L and FX3U-ENET-ADP are Ethernet-connectable. The FX3U-ENET-L can be used with the FX3U and FX3UC series (both Ver. 2.21 or later). The FX3U-... More Details >>
- No:22270
- Release Date:2018/08/30 13:48
-
Certificate of non-applicability to export MELSEC-F to other countries
For issuance of a certificate, please consult your local Mitsubishi representative. More Details >>
- No:22264
- Release Date:2018/08/30 13:48