Connecting local stations to the FX3U-16CCL-M
No, local stations cannot be connected to the FX3U-16CCL-M. Remote I/O stations, remote device stations, and intelligent device stations can be connected to... More Details >>
- No:24791
- Release Date:2019/02/28 09:06
-
The FX2N-16CCL-M cannot be set as the master station in the parameter setting. Use the FROM/TO instructions and setin the program. More Details >>
- No:25001
- Release Date:2019/04/23 10:39
-
Switching network between 10BASE-T and 100BASE-TX of the FX3U-ENET-L
It cannot be freely switched. It is automatically switched according to the auto detection function. More Details >>
- No:24964
- Release Date:2019/04/23 07:18
-
Using the FX3U-16CCL-M and FX2N-16CCL-M together
No, they cannot be added together. Only one FX3U-16CCL-M can be connected to one main unit. Multiple FX2N-16CCL-Ms can be connected to one main unit (dependi... More Details >>
- No:24954
- Release Date:2019/04/18 14:28
-
Number of GOTs (GOT1000 series) that can be connected to a FX3U-ENET-L
Up to two GOTs can be connected toa FX3U-ENET-L and MELSOFT connection needs to be set. More Details >>
- No:24933
- Release Date:2019/04/18 14:23
-
MELSOFT connection of the FX3U-ENET-L Ethernet interface block
Up to 2 connections can be opened. More Details >>
- No:24919
- Release Date:2019/04/17 11:40
-
Connecting the FX3U-ENET-L whose parameters have not been set
When writing parameters first time, write the parameters for Ethernet (data of FX Configurator-RN-L) from a personal computer to a programmable controller ma... More Details >>
- No:24790
- Release Date:2019/02/28 09:08
-
The main units with Ver.3.10 or later can read and write programs of the FX3 series connected to the intelligent device station and can monitor devices. (GX ... More Details >>
- No:24990
- Release Date:2019/04/23 10:37
-
Assignment of remote input device and remote output device of FX3U-16CCL-M
The remote input device and the remote output device cannot be assigned in network parameters. To assign them, create a program for updating data. For de... More Details >>
- No:24792
- Release Date:2019/02/28 09:08
-
The slave stations cannot be assigned to X/Y numbers. Use the auxiliary relay M. More Details >>