Set Pr.56 (Current monitor reference) to "10A". More Details >>
- No:21865
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
"n" in the address RWwn indicates a value determined by the station number setting. More Details >>
- No:21867
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Purchase the FR-A7NC if you are using the option with the FR-A700 or FR-F700P (F700).Purchase the FR-A7NC E kit if you are using the option with the FR-E700. More Details >>
- No:21902
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Yes. It is available by using the FR-A7AY (plug-in option). By setting Pr.307 (Setting for zero analog output) to "20" and Pr.309 (Analog output signal volta... More Details >>
- No:21246
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Since the initial value of Pr.13 (Starting frequency) is 0.5 Hz, the operation does not start unless 0.5 Hz or higher frequency is set. When 0.49 Hz is set i... More Details >>
- No:21251
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Automatic restart after instantaneous power failure
The inverter restart operation is disabled at turn-OFF of the CS signal while a value other than "9999" (with restart) is set in Pr.57. The terminals CS and ... More Details >>
- No:21255
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
When Advanced magnetic flux vector control (Pr.80, 81) is used, the machine speed constant is controlled. The inverter calculates the motor slip and compensa... More Details >>
- No:21374
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
The reactor built in the FREQROL-A201 series is intended to stabilize operation of the converter circuit and differs from the FR-BAL. Note that when performi... More Details >>
- No:21421
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , Options , Others
-
"8" display in offline auto tuning means forced stop by the operator. This means that you stopped operation before tuning completes. With this forced stop, ... More Details >>
- No:21527
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
1. Set Pr.162 to "10" (Frequency search at every start).2. You can ignore the setting if the motor excitation current is unknown. More Details >>
- No:21718
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ