Parameter No.79 (Operation mode)
You cannot cancel multi-speed command input. When the multi-speed command is input from the terminal, you cannot use the potentiometer. Use the inverter so t... More Details >>
- No:21467
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E500
-
Advanced magnetic flux vector control
To use Advanced magnetic flux vector control, basically set Pr.9, Pr.80, Pr.81, Pr.71, and Pr.800.Auto tuning is necessary in some cases. Set Pr.83, Pr.84, a... More Details >>
- No:21755
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700
-
To accept the current signal, the terminals AU (current input selection) and SD must be short-circuited. Check it.Note that this terminal AU is not prepared ... More Details >>
- No:21799
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Yes. More Details >>
- No:21871
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
You can select from the output power (in 0.01 kW units) and cumulative energy (in 1 kWh/0.01 kWh units). More Details >>
- No:21885
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Gain adjustment under the speed control
Since the lower limit has been internally set, 3% or less is recognized as 3%. More Details >>
- No:21016
- Release Date:2018/08/22 16:25
- Category: FREQROL-A800 , FREQROL-F800
-
No. They can be connected with the connection cable (FR-CB20[]). [] indicates cable length (1 m, 3 m, 5 m). More Details >>
- No:21081
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , Options , FREQROL-A800 , FREQROL-F800
-
No, it is not available. It is only available in the External operation mode or combined operation mode (PU speed command and External operation command (Pr.... More Details >>
- No:21192
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Refer to the FR-A700/F700/E700/D700 series TECHNICAL MANUAL (section 3.7.2) and the Technical News. The FR-A700/F700/E700/D700 series TECHNICAL MANUAL can be... More Details >>
- No:21263
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
When only the main circuit input power supply is cut off with the MC (when the power supply shutoff time is long), the main circuit undervoltage or instantan... More Details >>
- No:20833
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800