The answers are as follows:- Effect of reactorAttaching a reactor improves the power factor and suppresses harmonics.The AC reactor improves the power factor... More Details >>
- No:22092
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , Options
-
The trace data is stored in the built-in RAM of the inverter and deleted when the power is turned OFF or the inverter is reset. The data can be held with any... More Details >>
- No:21078
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800
-
Under Real sensorless vector control, the maximum wiring length is 500 m. Under Vector control with encoder, the maximum wiring length is 100 m. More Details >>
- No:21133
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-A700
-
"E.OSD" occurs when the rotation speed is not decreased for one second despite the start command (STF, STR) is turned OFF. More Details >>
- No:21159
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-A700
-
Install the resistor between the terminals PC and OH. More Details >>
- No:21160
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-A700
-
Leave the setting of Pr.96 as "3". It indicates that auto tuning has been completed and the motor constant has been read. When it is changed unnecessarily, t... More Details >>
- No:21352
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700
-
The inverters FR-A200 and V200 do not support CC-Link. (The FR-A500 series supports CC-Link.) Use the open collector output and relay output card when combin... More Details >>
- No:21504
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , Others , FREQROL-V200 , FREQROL-A200
-
Heat generation quantity of FR-A500
The heat generation quantity of the FR-A520-5.5K is 310 W. (Reference: The heat generation quantity of the FR-A220E-5.5K is 330 W.) For other capacities, ref... More Details >>
- No:21515
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
If Pr.544 (CC-Link extended setting) is set to other than "0", you do not need to change Pr.544 (CC-Link extended setting).Write the extended setting of the ... More Details >>
- No:21834
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Set Pr.340 (Communication startup mode selection) to "1" or "2".Also, by setting Pr.79 (Operation mode selection) to "0", "2", or "6", the inverter enters th... More Details >>
- No:21879
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P