FAQ


FAQAbout Products

- FAQ > Drive Products > Inverters-FREQROL
FAQ
Keyword Search
Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
Up to 30 m. (To avoid noise and voltage drop) More Details >>
- No:21910
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Error of the communication option
E.OP1 indicates the communication line error. E.1 indicates a hardware fault of the communication option. (It is judged as the hardware fault when the commun... More Details >>
- No:20805
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , Plug-in Options
-
Up to three inverters can be connected. When more than four inverters are connected, the inverters may not be recognized because of the voltage drop. More Details >>
- No:21053
- Release Date:2018/08/22 16:25
- Category: FREQROL-A800 , FREQROL-F800
-
Countermeasure against noise on input side
In general, the line noise filter (FR-BLF) is used against the power supply noise. The AC reactor also works. As other countermeasures:- Use a metal conduit ... More Details >>
- No:21517
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , Others , FREQROL-A200
-
The relationship between the acceleration/deceleration reference frequency and acceleration/deceleration time does not change between the PU operation and ex... More Details >>
- No:21694
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Set Pr.79 (Operation mode) to "3".When a signal is input to the terminal RL, the inverter starts operating at the frequency set with Pr.6 (Multi-speed settin... More Details >>
- No:21791
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Check the setting of Pr.79 (Operation mode).If the setting value is "2", frequency commands from an external terminal is effective and the frequency setting ... More Details >>
- No:21797
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
You can do so by assigning the terminal AU.Assign the terminal AU to an unused terminal.(For example, when assigning AU to the terminal RL, set Pr.180 = 4.)B... More Details >>
- No:21915
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
The sine wave filter can be applied only under V/F control. When Pr.72 PWM frequency selection is set to 25, V/F control is set automatically. The applicable... More Details >>
- No:21068
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , Options , FREQROL-A800 , FREQROL-A700
-
Power is supplied only to the control power supply, and thus this enables communication, parameter setting through the operation panel or an USB memory devic... More Details >>
- No:21097
- Release Date:2018/08/22 16:25
- Category: FREQROL-A800 , FREQROL-F800
1021-1030 of Total 1306