If you are using CC-Link just to monitor the inverter and using the analog signal and multi-speed setting to set the frequency, you need to input them extern... More Details >>
- No:21900
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Set Pr.550 (NET mode operation command source selection) to "2" (PU connector is the command source).When operating the inverter using the USB connector, set... More Details >>
- No:21904
- Release Date:2018/08/22 16:30
- Category: FREQROL-E700
-
You can do so by assigning the terminal AU.Assign the terminal AU to an unused terminal.(For example, when assigning AU to the terminal RL, set Pr.180 = 4.)B... More Details >>
- No:21915
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Checking terminals used:Are the terminals MRS and RES open?Are the terminals STR and SD short-circuited correctly?Is the voltage/current switch of the termin... More Details >>
- No:21916
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-F700PJ
-
You can connect up to three inverters to a single external frequency setting potentiometer to control them. More Details >>
- No:21917
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Removal of the jumper between the terminals P1 and P is not necessary unless you are using the DC reactor.Set Pr.30 = "0" when using the brake unit.Since set... More Details >>
- No:21921
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Change Pr.18 (High speed maximum frequency) to 400 Hz.If you are using the analog command to set the frequency, calibrate the 400 Hz frequency with Pr.903. More Details >>
- No:21931
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Encoder cable length restriction
If the cable length is longer than 100 m, speed may not be read correctly due to voltage drop and waveform deformation of the encoder signal. Therefore, use ... More Details >>
- No:21932
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-V200
-
Acceleration/deceleration time
You cannot set and/or enable the acceleration time and deceleration time individually. More Details >>
- No:21938
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , SC-A
-
Second deceleration time setting
Your suggestion is fine, but note that deceleration stop is naturally not available in case of an inverter error.In addition, considering regenerative power,... More Details >>
- No:21939