FAQ
FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL
FAQ
Keyword Search
Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
Use the FR-A740. Basically, select the capacity according to the calculation result of "rated inverter output current ? rated motor current × 1.1". More Details >>
- No:21244
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Set Pr.71 (Applied motor), Pr.80 (Motor capacity), Pr.81 (Number of motor poles), and Pr.800 (Control method selection). More Details >>
- No:21245
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Normally, the auto tuning condition depends on the combination of the inverter and motor (including wiring to the motor), perform auto tuning each time. The ... More Details >>
- No:21293
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700PJ
-
Auto tuning can be performed because the motor is one rank lower than the inverter capacity. More Details >>
- No:21351
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700PJ
-
"OV3" occurs during an inverter stop.
An error may have occurred due to the rise of the main circuit voltage of the inverter caused by a power surge. Check for the power supply voltage. If the ca... More Details >>
- No:21383
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A024
-
Yes. However, write the setting data to the RAM of the inverter.Set RWw1 in the setting value and turn ON the frequency setting command RYD.To continuously s... More Details >>
- No:21825
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
1. It depends on how Pr.338 (Communication operation command source) and Pr.339 (Communication speed command source) are set.2. The external terminal reset i... More Details >>
- No:21838
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Switching between PU and NET operation modes
Set Pr.340 (Communication startup mode selection) to "10".The operation mode can be switched between PU and NET by assigning X65 (PU-NET operation switching)... More Details >>
- No:21878
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Regenerative overvoltage protection (E.OVT).This error occurs when the regenerative power returns from the motor to the inverter (for example, during deceler... More Details >>
- No:21991
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-F400
-
1. To perform emergency stop, it is recommended to have the motor coast and stop it using a mechanical brake.In this case, the output stop (MRS) signal is in... More Details >>
- No:22103
- Release Date:2018/08/22 16:31
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-E500