FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL
FAQ
Keyword Search
Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
The instantaneous power failure error occurs when the power is turned ON instantaneously (within 100 ms) after the power is turned OFF. When the motor is coa... More Details >>
- No:21388
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL
-
After inputting the start signal performing the tuning, output the output frequency. The tuning ends in approximately 500 ms in maximum after started. Durin... More Details >>
- No:21372
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Reverse operation is enabled by changing the setting of Pr.40. More Details >>
- No:21287
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-F700PJ
-
Pr.38 of the E500 corresponds to Pr.125 (Terminal 2 frequency setting gain frequency) of D700. Pr.39 of the E500 corresponds to Pr.126 (Terminal 4 frequency ... More Details >>
- No:21254
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-D700
-
Checking bit state by CC-Link communication
Because the H0F monitor only observes the ON/OFF of the hardware, it cannot be checked. More Details >>
- No:21230
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
System environment variable of the Modbus-RTU communication
They are not received during the operation. They are also not received if the command authority does not exist in the communication. When they are executed i... More Details >>
- No:21223
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
System environment variable of the Modbus-RTU communication
It decelerates and stops. The operation is the same as the one when the Bit of forward rotation command and reverse rotation command are turned OFF. More Details >>
- No:21222
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
Reading during the operation is possible. However, when writing is performed during the operation, "rE2" (parameter write error) occurs. More Details >>
- No:21215
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
It is fixed to 5 kHz. More Details >>
- No:21211
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
It is accumulated even when only the control power is ON. More Details >>
- No:21208
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
1041-1050 of Total 1292