FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL
FAQ
Keyword Search
Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
Printing files saved in the previous version of FR-Configurator
The parameter file of FR-SW3 cannot be printed using FR-SW2. The latest version of FR-SW3 can be downloaded from the Mitsubishi Electric FA Global Website. U... More Details >>
- No:21315
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
No parameter can be used to directly set this time.Changing Pr.9 (Electronic thermal O/L relay) changes the time. More Details >>
- No:21769
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
For the FR-E700, only the terminal FM allows for variable output and the output is a pulse signal. Therefore, it cannot be directly input to the programmable... More Details >>
- No:21682
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Number of stations that can be set in FR Configurator
The station numbers that can be set differ depending on the version of FR-Configurator (FR-SW3-SETUP-WJ) setup software. For Ver.2.00 or later, station numbe... More Details >>
- No:21305
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Change Pr.161 (Frequency setting/key lock operation selection) to "1" (potentiometer mode). More Details >>
- No:21792
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
This is due to specifications that multi-speed selection is prioritized and setting with the setting dial is ignored.The setting dial is effective when multi... More Details >>
- No:21843
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
You can set reserved and invalid stations.The Instruction Manual instructs to set consecutive numbers because the master regards an empty number as an error. More Details >>
- No:21905
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Cause of overcurrent (OC2) at constant speed
First of all, capacity reduction of the main circuit electrolytic capacitor is probable. Usually, the electrolytic capacitor is replaced every 5 years on ave... More Details >>
- No:21407
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A100
-
No problem.LEDs "PU" and "EXT" indicate that Pr.79 is set to "3"."MON" indicates that the operation status is monitored."RUN" indicates that the inverter is ... More Details >>
- No:21776
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-F700PJ
-
The station number and baud rate were set using the dial for the FR-A5NC, but parameter is used for the FR-A7NC. Pr.542 (Communication station number (CC-Lin... More Details >>
- No:21248
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
1051-1060 of Total 1292