Using both types of power factor improving reactors
Yes.By using both types of reactors together, you can reduce the outgoing harmonic current.For examples of harmonics reduction, refer to the value in the har... More Details >>
- No:21995
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , Options
-
Built-in potentiometer and current input switching control
For setting the frequency, you cannot switch between the operation panel potentiometer and current input from an external source.To switch between the extern... More Details >>
- No:21985
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E500
-
Using existing potentiometer by replacing inverter
It is OK if the resistance value of the speed varying potentiometer's resistance is 2 kΩ.Use the speed varying potentiometers used with the existing inverter... More Details >>
- No:21962
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL
-
Rated capacity related to harmonic suppression guidelines
The usual inverter input current is determined not by the inverter capacity but by the motor capacity (motor load).Therefore, the input side capacity is not ... More Details >>
- No:21961
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , Others
-
Take the following countermeasure:1. If the thermal trips in low-speed operation, trips can be avoided, depending on the external thermal relay operation cha... More Details >>
- No:21954
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E500
-
Short-circuiting frequency setting terminals
You can short-circuit the terminals 10 and 2.If you are considering to perform operation at the maximum frequency, consider using the high-speed command RH o... More Details >>
- No:21951
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL
-
Using built-in potentiometer and multi-speed together
Yes. Set Pr.79 = 3. (Input the start signal from an external source.) More Details >>
- No:21950
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E500
-
Electronic thermal O/L relay setting
Set Pr.9 to the rated current at 50 Hz or a value 1.1 times as the rated current at 60 Hz.You can specify the motor type with Pr.71 (Applied motor). For a co... More Details >>
- No:21941
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL
-
Using a higher grade power factor improving reactor
Using a reactor under a load lighter than the rated capacity slightly spoils its effect in improving the power factor.Therefore, you should use a reactor wit... More Details >>
- No:21935
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , Options
-
Use the setting dial to set the frequency with the FR-E700.You can also use the setting dial to set the parameters.(By setting Pr.161, you can use the settin... More Details >>
- No:21918
- Release Date:2018/08/22 16:30
- Category: FREQROL-E700