Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
The noise filter is not built-in the FR-E700 series. It is built in the FR-A700/F700 series with the 55K or lower capacity. More Details >>
- No:21276
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700
-
The ferrule terminal or single wire can be used for the control circuit wiring. More Details >>
- No:21275
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700
-
When the built-in brake resistor is used, the regenerative brake duty is as follows:200 V 0.4K to 3.7K: 3%, 5.5K to 7.5K: 2%400 V 0.4K to 7.5K: 2 % The capac... More Details >>
- No:21273
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-A700
-
Real sensorless vector control
No, Real sensorless vector control cannot be used in the FR-E700. More Details >>
- No:21269
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700
-
They are insulated. More Details >>
- No:21242
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
Pr.268 (Monitor decimal digits selection) during CC-Link communication
No, it is not changed. Pr.268 is the parameter for the operation panel. More Details >>
- No:21241
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
Writing set frequency by CC-Link communication
No error will occur because up to 400 Hz that is the upper limit of the setting range can be written. More Details >>
- No:21229
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
LED blinking under encoder feedback control
The following may be the cause. - No encoder power supply. - The setting of Pr.359 (Encoder rotation direction) is reversed. - The signal from the encoder is... More Details >>
- No:21219
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
Reading during the operation is possible. However, when writing is performed during the operation, "rE2" (parameter write error) occurs. More Details >>
- No:21215
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
No. During JOG operation, deceleration stop is performed even though Pr.250 is set. More Details >>
- No:21199
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
1071-1080 of Total 1292