1. Yes. 2. Set Pr.17 to "2". 3. If the start signal is ON, the operation continues even the emergency stop is OFF. More Details >>
- No:21359
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Switching between external operation and NET operation
You can write frequency setting by setting Pr.339 (Communication speed command source) to "0". More Details >>
- No:21687
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Since the percent value read by the calibration parameter C7 indicates that the voltage of 10 V is internally detected as 101.0%, use 101.0% as is.If you cha... More Details >>
- No:21740
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Set Pr.52 (PU/DU main display data selection) to "5".Set the monitor as the third monitor, frequency -> current -> setting frequency. More Details >>
- No:21745
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
You can use the setting dial together with the terminal 4.Set Pr.79 (Operation mode) to "3" (Combined operation mode) and assign the AU signal to an unused t... More Details >>
- No:21856
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
When Pr.80 and Pr.81 are set to the value other than "9999", control other than V/F control is performed. For the FR-F700(P) FR-D700, and FR-F700PJ, Pr.81 is... More Details >>
- No:21259
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Pr.244 (Cooling fan operation selection) controls turning ON/OFF of the cooling fan and is initially set to "1". When the inverter is powered ON, the cooling... More Details >>
- No:21670
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Yes.Set Pr.19 (Base frequency voltage) to "200 V".200 V output will be obtained during 60 Hz operation. More Details >>
- No:21717
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
It cannot be avoided by using parameters. More Details >>
- No:21724
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
This parameter cannot be changed in the external operation mode.Change Pr.77 (Parameter write selection) to "2" before changing the setting of Pr.72. More Details >>
- No:21743
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ