FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL
FAQ
Keyword Search
Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
To set the motor to coasting state, the following methods are available: 1. Set Pr.250 (Stop selection) to "0" and turn OFF the start command. 2. Short the t... More Details >>
- No:21271
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Not possible.Instead of FR-DU07, use FR-PA07 (or FR-PU07) as an operation panel for FR-E700. More Details >>
- No:21708
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , Others , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
If you try to change a parameter in other than the PU operation mode, the mode specification error "Er4" may occur.Set the parameters in the PU operation mod... More Details >>
- No:21778
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
It seems that calibration for 20 mA current signal input is not correct.Use the calibration parameters "126" and "C7" to calibrate the inverter.Perform calib... More Details >>
- No:21785
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Set Pr.13 (Starting frequency) or Pr.2 (Lower limit) to "5 Hz".Also set Pr.10 (DC injection brake operation frequency) to "5 Hz".The inverter does not operat... More Details >>
- No:21790
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Normally, any of the PU, EXT, or NET LED turns ON.Check if the parameter unit FR-PU04/FR-PU07 or operation panel FR-PA07 is externally connected to the PU co... More Details >>
- No:21803
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
1. By setting Pr.158 (Terminal AM function selection) to "21" (Reference voltage output), 10 V is output from the terminal AM.2. Read Pr.901 in the PU operat... More Details >>
- No:21936
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-F500 , FREQROL-A200 , FREQROL-A100
-
Suggestion for replacement of inverters
We do not offer book type inverters. Therefore, the S500 is recommended to replace the Z123 because of its compact design. If regenerative driving matters, c... More Details >>
- No:22104
- Release Date:2018/08/22 16:31
- Category: Inverters-FREQROL , FREQROL-Z123 , FREQROL-Z024
-
The Radio Act applies to the products used for the purpose of the radio waves. Inverters are used for motor drive and thus out of the scope. More Details >>
- No:20994
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800 , FREQROL-E700 , FREQROL-D700
-
Connecting ammeter to output side
Yes. Use a moving-iron type ammeter. However, if the carrier frequency exceeds 5 kHz, do not use that meter since an overcurrent losses produced in the inter... More Details >>
- No:21681
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ