Input "0" to the bit not to be sent. More Details >>
- No:20970
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , Options
-
Yes. More Details >>
- No:20959
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , FREQROL-A700
-
When the PG24 terminal and the PG terminal are shorted, 24 VDC power for the encoder can be supplied from the PG24 terminal. More Details >>
- No:20954
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , Plug-in Options
-
Because RSO (converter reset) of the HC2 is connected to RES of the inverter, the inverter is reset along with the HC2 reset. (Refer to the wiring diagram in... More Details >>
- No:20948
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , Options
-
The initial value of Pr.872 is set to "1" (Valid) because the A701 have regeneration unit built-in and an overvoltage may occur when the regenerative operati... More Details >>
- No:20945
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , FREQROL-A700
-
It depends on machine specifications. It depends on the accuracy of the line speed input and parameter setting of material thickness. More Details >>
- No:20927
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL
-
The frequency setting in the communication cannot be used together with FR-A8AX. The priority of the FR-A8AX is equal to the second terminal analog input and... More Details >>
- No:20917
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , Plug-in Options
-
Monitoring function of the FR-A800-R2R
Line speed command and Line speed pulse monitor can be monitored while the operation is stopping. Actual line speed monitor becomes "0" while the operation i... More Details >>
- No:20914
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , FREQROL-A800
-
The count is resumed from 0. Thus, the times of the overflow is reset. More Details >>
- No:20902
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL
-
Terminal 2 input selector switch when the PTC thermistor is connected
When the DIP switch is changed to I, it does not operate normally because the internal resistance changes. More Details >>
- No:20901
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL