FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL
FAQ
Keyword Search
Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
The power supply voltage may have dropped.Read the converter output voltage monitor (Pr.55 = 8) and check if Converter output voltage monitor/√2 is within th... More Details >>
- No:21820
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
The FR-DU07 cannot be used with the FR-E700, FR-D700, or FR-F700PJ. More Details >>
- No:21854
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-F700PJ
-
You can connect up to three inverters to a single external frequency setting potentiometer to control them. More Details >>
- No:21917
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Set the parameters below. For other parameters, keep the initial settings.1. Set Pr.122 (Communication check time interval) to other than "0". ("9999" is OK.... More Details >>
- No:21986
- Release Date:2018/08/22 16:30
- Category: Engineering Software
-
The following is the case for the FREQROL-A500 series:1. When the R phase or S phase is lost, the inverter stops since it loses the control power supply.2. W... More Details >>
- No:22010
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Vector control cannot be selected unless Pr.862 is set to 1. Only the first motor is supported in the motor setting of FR Configurator2. More Details >>
- No:20840
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , Engineering Software , FREQROL-A800
-
Residual voltage at the output shutoff
The rotation speed has almost no effect. The residual voltage increases when the torque boost is increased, but no adjustment is required. More Details >>
- No:20906
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800
-
No, it is not available. It is only available in the External operation mode or combined operation mode (PU speed command and External operation command (Pr.... More Details >>
- No:21192
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Blinking of the "RUN" LED on the panel suggests that the frequency command may not be input. Create a frequency setting data as for the forward rotation comm... More Details >>
- No:21301
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Frequency monitor display fault
This can occur if the parameter unit window display is set to "Frequency setting value". If the screen display selection (first monitored window) is set to "... More Details >>
- No:21526
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A200
1141-1150 of Total 1292