The storage areas for the sequence programs and for the parameters of the inverter are different. More Details >>
- No:20958
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800
-
When the PG24 terminal and the PG terminal are shorted, 24 VDC power for the encoder can be supplied from the PG24 terminal. More Details >>
- No:20954
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , Plug-in Options
-
No, it does not affect the control. When a swinging frequency is set in Pr.1074, the setting values in Pr.1077 to Pr.1079 are not referred. When Pr.1074 is s... More Details >>
- No:20952
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , FREQROL-A800
-
The FR-CC2 has a built-in EMC filter (radio noise filter). More Details >>
- No:20951
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL
-
Sampling time of FR Configurator2
It depends on the mask count. It is approximately 0.125 [ms] (mask count: 1) to 20 [ms] (mask count: 30). More Details >>
- No:20950
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , Engineering Software
-
Because RSO (converter reset) of the HC2 is connected to RES of the inverter, the inverter is reset along with the HC2 reset. (Refer to the wiring diagram in... More Details >>
- No:20948
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , Options
-
For output signals, up to 10 points (RXn2 to RXB) can be assigned. It is possible if the number of the importing signal points are within this range. More Details >>
- No:20943
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , Plug-in Options
-
The internal transistor of the HC2 stops by turning on the SOF signal and stopping the converter. As a result, regenerative driving is not performed. However... More Details >>
- No:20941
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , Options
-
Waiting time at the instantaneous power failure
The count is started from the power failure. The count is started after the power restoration or reset release when the power failure period is too long, or ... More Details >>
- No:20939
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL
-
Difference in the monitor function
The same value is displayed in the initial setting. When negative output is enabled by setting "0" to Pr.290 (Monitor negative output selection), there are f... More Details >>
- No:20938
- Release Date:2018/08/22 16:25