Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
The X114 signal is for switching the control to the dancer control or tension sensorless torque control. The signal input becomes invalid during operation be... More Details >>
- No:20845
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , FREQROL-A800
-
Leakage current of the FR-HAL/FR-HEL
It is less than 1 mA. More Details >>
- No:20844
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , Options
-
No, it is not. It is released by the inverter reset that releases E.OHT. More Details >>
- No:20843
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , FREQROL-A800
-
Perform the writing after turning ON the SOF, or after stopping the FR-HC2 by pressing the STOP button. Wire the RDY signal so that the inverter stops when t... More Details >>
- No:20842
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , Options
-
Combination of the FR-F800 and FR-A8TAT
Yes, it can. For the capacity of 37K or more, use the included bracket for installation. More Details >>
- No:20841
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , Options , FREQROL-F800
-
For the 200 V type, the leakage current at the delta connection is 5 mA. For the 400 V type, it is 10 mA. More Details >>
- No:20835
- Release Date:2018/08/22 16:24
- Category: Options
-
S-shape acceleration/deceleration of the FR-D700
It does not change even when General-purpose magnetic flux vector control is performed. Pr.3 is the inflection point of the S-shape. More Details >>
- No:20834
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , FREQROL-D700
-
Frequency search of the FR-A800/FR-F800
DC voltage is applied when Pr.162 = 0, and AC voltage is applied when Pr.162 = 3 or 13. For the AC, the operation is easier to continue than the DC and the i... More Details >>
- No:20831
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800
-
It is possible when Pr.23 = 0 (Current limit at regenerative driving). More Details >>
- No:20826
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , Options
-
Ver.1.11M or later of FR Configurator2 support the FR-A806. More Details >>