Pr.30 = "1" and Pr.70 = "0". More Details >>
- No:21143
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , Options , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Switching External operation, PU operation
Setting Pr.79 (Operation mode) to "6" sets the switchover mode. Pressing the "PU/EXT" key on the operation panel during External operation switches the mode ... More Details >>
- No:21289
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Parameter copy method of FR-Configurator
The data can be copied to other inverters. 1. Save the parameter of the inverter to be copied with extension "pr3" by using "export". 2. Replace the connecte... More Details >>
- No:21307
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
When the wire between the 400 V inverter and motor is long (20 m or longer), surge voltage occurs momentarily. This voltage is as two or more times as the DC... More Details >>
- No:21404
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-F500 , FREQROL-A024 , FREQROL-E500 , FREQROL-V200 , FREQROL-A200 , FREQROL-A100
-
If Pr.79 = 3, PU and EXT turn ON. Switching between PU and EXT is not available. Turn the setting dial to set the frequency and press the SET key to accept it. More Details >>
- No:21695
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
What happens if reset occurs during operation?
This is because when the inverter restarts while the motor is coasting, an overcurrent trip can occur during the restart process. However, the recent types o... More Details >>
- No:21477
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A024 , FREQROL-E500 , FREQROL-V200 , FREQROL-A200 , FREQROL-A100 , FREQROL-U100 , Common
-
Error "E.UVT" (undervoltage protection)
The possible causes of the error UVT are as follows.- Low power supply voltage - Insufficient power supply capacity - Damage or failure Check the power suppl... More Details >>
- No:21295
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
The regenerative overvoltage shutoff protective function is provided since the terminal voltage of the internal capacitor of the inverter can rise abnormally... More Details >>
- No:21544
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL
-
Surge voltage of 400 V inverter
No. Although the carrier frequency increases or decreases the switching count, the switching speed is the OFF-to-ON speed of the IGBT element of the inverter... More Details >>
- No:21401
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-F500 , FREQROL-A024 , FREQROL-E500 , FREQROL-V200 , FREQROL-A200 , FREQROL-S500 , FREQROL-A100
-
Deceleration overvoltage (E.OV3)
While the FREQROL-Z200 series and A500 series have a brake resistor built in the capacity up to 7.5K, the FREQROL-E500 series does not have a built-in brake ... More Details >>
- No:21993
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E500