FAQ


FAQAbout Products

- FAQ > Drive Products > Inverters-FREQROL
FAQ
Keyword Search
Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
Adjust the terminal 2 bias with Pr.C2 and Pr.C3, and the terminal 2 gain with Pr.125 and Pr.C4. Set Pr.C2 (Terminal 2 frequency setting bias frequency) to 20... More Details >>
- No:21685
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
You can vary the carrier frequency within the range of 0.7 to 14.5 kHz, and it is initially set to 1 kHz that generates low noise and leakage current. You ca... More Details >>
- No:21607
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A024
-
Sensitivity current of earth leakage circuit breaker
The rated sensitivity current of the earth leakage circuit breaker can be calculated using the following equation. If the result is 30 mA or less, the NV-FA ... More Details >>
- No:21547
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , Peripheral devices
-
Direct driven start by power supply
The warning "Do not use a magnetic contactor on the inverter input for frequent starting/stopping of the inverter." is indicated in the precautions at the be... More Details >>
- No:21458
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E500
-
It is considered to be caused by inverter PWM control. It can be suppressed by raising the PWM carrier frequency (Pr.72), but the entire noise and leakage cu... More Details >>
- No:21428
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E500
-
The RS485 communication is explained in the FREQROL-E500 Instruction Manual. This Instruction Manual is published on the member's page of Mitsubishi Electric... More Details >>
- No:21426
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E500
-
Remote operation of the inverter
The wiring length of the start signal (STF etc.) is 30 m or less. The circuit voltage of the control input signals (terminal STF etc.) is 24 VDC and the volt... More Details >>
- No:21380
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
For the Instruction Manual "Applied", fill in the request sheet which is included in the last part of the Instruction Manual "Basic", and fax it to the speci... More Details >>
- No:21341
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Fault output terminal A, B, and C
Set the rated motor current to Pr.9. It is the heat protection setting for the motor, and thus the inverter does not shutoff immediately at the specified cur... More Details >>
- No:21324
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
When Pr.259 (Main circuit capacitor life measuring) is set to "1", the life diagnosis is ready. Turning OFF the power supply starts measuring the life of the... More Details >>
- No:21283
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
131-140 of Total 1306