When the brake sequence function is enabled, the RT signal is disabled and the stop-on-contact control cannot be performed. More Details >>
- No:21209
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
It is not output in the JOG operation mode. More Details >>
- No:21214
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
When the second torque limit is used, the settings of Pr.816 and 817 are valid. More Details >>
- No:21218
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
LED blinking under encoder feedback control
The following may be the cause. - No encoder power supply. - The setting of Pr.359 (Encoder rotation direction) is reversed. - The signal from the encoder is... More Details >>
- No:21219
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
LED blinking under encoder feedback control
The Z-phase signal may be connected to the A-phase or B-phase incorrectly. Check the wiring. More Details >>
- No:21220
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
Remote input signal of CC-Link communication
The signal becomes 0 when the RES signal is turned ON. More Details >>
- No:21238
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
Pr.38 of the E500 corresponds to Pr.125 (Terminal 2 frequency setting gain frequency) of D700. Pr.39 of the E500 corresponds to Pr.126 (Terminal 4 frequency ... More Details >>
- No:21254
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-D700
-
It can be driven by connecting single-phase 200 V to the terminals R and S. In this case, the load current must be one-third or less of the inverter rated cu... More Details >>
- No:21282
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700
-
Yes. The model is FR-E710W. The input is single-phase 100 V, but the output is three-phase 200 V. More Details >>
- No:21320
- Release Date:2018/08/22 16:27
- Category: FREQROL-E700
-
Check the setting value of Pr.73. Or check Pr.C4 (Terminal 2 frequency setting gain) for the percentage of the voltage that is actually applied. For the FR-E... More Details >>