FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL
FAQ
Keyword Search
Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
The ferrule terminal or single wire can be used for the control circuit wiring. More Details >>
- No:21275
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700
-
The noise filter is not built-in the FR-E700 series. It is built in the FR-A700/F700 series with the 55K or lower capacity. More Details >>
- No:21276
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700
-
It can be driven by connecting single-phase 200 V to the terminals R and S. In this case, the load current must be one-third or less of the inverter rated cu... More Details >>
- No:21282
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700
-
It is available since June, 2007. The model is FR-E7TR. More Details >>
- No:21300
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700
-
Comparison of the speed change rate
Speed fluctuation ratio differs depending on the control method as follows. - V/F control?????????2 to 5% (At the encoder feedback: 0.02%)- General-purpose m... More Details >>
- No:21377
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL
-
Priority of multi-speed setting and frequency setting signals
For frequency setting, multi-speed setting is prioritized over current input. Therefore, when the multi-speed signal is input, the inverter switch to multi-s... More Details >>
- No:21400
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL
-
The current value can be displayed on the operation panel without regard to the setting of monitor-related parameters. As the current value remains 0 A, the ... More Details >>
- No:21405
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL
-
Durability in multi-speed setting
1. You can set the minimum time by setting the acceleration/deceleration time and acceleration/deceleration reference frequency. 2. No problem with the termi... More Details >>
- No:21437
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
There is a 10 ms delay after the inverter recognizes the start command (STF OR STR) before it starts decelerating. The delay is 10 ms. A delay of 100 ms is i... More Details >>
- No:21445
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Difference between use with A100 and other types
Similarly to the FR-A200 and A500, four or more filters should be used also for the FR-A100. In short, it is OK if the wire penetrates the filter four times... More Details >>
- No:21468
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , Options
221-230 of Total 1292