FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL
FAQ
Keyword Search
Inverters-FREQROL
FAQ within [ Inverters-FREQROL ]
-
Proper use of AC reactor and DC reactor
1. ACL has the input power factor of approximately 90% and DCL has the input power factor of approximately 95%. Therefore, DCL has a higher input power facto... More Details >>
- No:21949
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , Options
-
1. By setting Pr.158 (Terminal AM function selection) to "21" (Reference voltage output), 10 V is output from the terminal AM.2. Read Pr.901 in the PU operat... More Details >>
- No:21936
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-F500 , FREQROL-A200 , FREQROL-A100
-
Since Pr.125 (Terminal 2 frequency setting gain frequency) is initially set to 60 Hz, change it to 85 Hz. More Details >>
- No:21907
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
You can set reserved and invalid stations.The Instruction Manual instructs to set consecutive numbers because the master regards an empty number as an error. More Details >>
- No:21905
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Create a ladder program to read inverter faults on the programmable controller.Set the instruction code (H74-H77) and turn ON the instruction code execution ... More Details >>
- No:21886
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Yes. You can use the setting dial of the inverter to set the frequency as well as change the parameter values. More Details >>
- No:21846
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Set Pr.146 (Built-in potentiometer switching) to "0".This allows for using the potentiometer built in the FR-PA02 to set the frequency.(Set this parameter to... More Details >>
- No:21729
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-F700PJ
-
For the FR-E700, only the terminal FM allows for variable output and the output is a pulse signal. Therefore, it cannot be directly input to the programmable... More Details >>
- No:21682
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
1. Yes. 2. Set Pr.17 to "2". 3. If the start signal is ON, the operation continues even the emergency stop is OFF. More Details >>
- No:21359
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
No, it cannot. More Details >>
- No:21253
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
231-240 of Total 1292